Pressurized plumbing without external separator – Nortec LiveSteam v.2 User Manual

Page 29

Advertising
background image

LS Installation Manual | 26

Pressurized Plumbing without External Separator

1” Air Gap

Drain

Strainer

Manual Shut-Off
Valve (By Others)

Pressurized
Steam Main

6” min.

Return to non-pressurized
floor drain

Pressurized condensate
return main

Tap steam from top of
pressurized steam main


Note: The SAM-e header functions as a steam separator, therefore an external
steam separator is not required.


















• Steam components in grey are provided by Nortec.
• Tap steam from top of pressurize steam main to avoid excess condensate.
• Condensate from SAM-e to be returned to atmospheric floor drain.

When pressurized steam enters the SAM-e, the pressure drops down to almost atmospheric
pressure. Therefore, it must be drained atmospherically, and the use of a condensate pump
(rated for 212ºF) must be used to raise the condensate to a higher elevation.





Advertising
This manual is related to the following products: