25 | LS Installation Manual

SAM-e with Pressure Steam

Pressurized Plumbing with External Separator

Strainer

Manual Shut-Off
Valve (By Others)

Pressurized
Steam Main

F & T Steam Trap

Duct/AHU Width

Duct/AHU

Height

Separator

Actuator & Valve

Pressurized condensate
return main

1” Air Gap

Drain

Manual Shut-Off
Valve (By Others)

6” min.

6” Min

Return to non-pressurized
condensate return main

Tap steam from top of
pressurized steam main

• Steam components in grey are provided by Nortec.
• Tap steam from top of pressurize steam main to avoid excess condensate.
• Condensate from separator to be returned to pressurized condensate main.
• Condensate from SAM-e to be returned to atmospheric floor drain.

When pressurized steam enters the SAM-e, the pressure drops down to almost atmospheric
pressure. Therefore, it must be drained atmospherically, and the use of a condensate pump
(rated for 212ºF) must be used to raise the condensate to a higher elevation.