5 notes on operation, 1 important notes on operation, 2 recommended regular checks during operation – Nortec ME Direct Feed User Manual

Page 23: Notes on operation, Important notes on operation, Recommended regular checks during operation

Advertising
background image

23

Operation

4.5

Notes on operation

4.5.1 Important notes on operation

If your system is equipped with the optional Nortec control unit and the optional purge valve, the water

supply line is purged

every 20 hours for approximately 3 minutes in order to flush water supply line.

The Nortec stage control unit will also drain the hoses that supply water to the distribution header dur-

ing these 3 minutes.

4.5.2 Recommended regular checks during operation

During operation the Nortec ME Control has to be checked periodically in accordance with the table below.

Operations Checks

Daily

Weekly

Monthly

Quarterly

Monitor humidity/temperature control

Check for any low humidity/temperature concerns

Check any alarms on BMS

Visible check for:

– No water leakage (air on and air off side)

– system components for correct fixing and any da-

mage

– electric installation for any damage.

Matrix media is saturated (relative to demand signal)

Condition of tanks and air on matrix is clean

Inspect and determine replacement frequency of se-

diment filter

Condition of tanks are clean (clean as required)

If the checks reveal any irregularities (e.g. leakage, error indication) or any damaged components take

the Nortec ME Control out of operation as described in chapter 4.6 – Decommissioning the system.

Then, have the malfunction eliminated or the damaged component replaced by a well trained specialist

or a service technician from your Nortec representative.