5.4

Dismantling and installation of components for maintenance

5.4.1 Dismantling and installation of the evaporative module

1. Take the Nortec ME Direct Feed out of operation as described in chapter 4.6 – Decommissioning

the system and allow to drain and dry.

2. Switch the AHU off, and isolate the power and water supply to the AHU.
3. Disconnect distribution hoses from the connectors on the distribution heads, the wall feed-throughs

(if applicable) and the hydraulic manifold.

4. Remove droplet separator boxes (column by column):

• Remove upper separator brackets.
• Remove bank of separator boxes.
• Remove lower separator brackets.

5. Remove evaporative cassettes (column by column):

• Push box upwards and remove.

6. Remove distribution headers assemblies from topmost evaporative cassettes:

• Remove plastic rivets fixing the distribution header assembly to the evaporative cassette.
• Carefully lift off the distribution header assembly.

7. Remove the cross bar (remember position).

Clean dismantled components, water tank, frame structure, blanking plates and air duct as described in

chapter 5.3 – Maintenance guide. If all components have been cleaned and dried, assemble the evapo-

rative module in the reverse dismantling order. Replace any defective components with new ones.

5.5

Consumables Guide

Common consumables

Description

Standard Frequency (month)

DISIFIN XL

1

Disinfection chemical (sourced locally)

6

Descaling chemical (sourced locally)

as required

Inlet flow restrictor

24

Distribution header feed hose

24

Evaporative matrix cassette

– Wholesome mains water

– RO water

36 - 60

60 - 84 +