26 Maintenance

5.2

Maintenance Intervals

In order to maintain operational safety and hygienic demands the Nortec ME Direct Feed must be serviced

at regular intervals. The time interval for the complete system service is to be adapted to the operating

conditions. The hygiene status depends mainly on the quality of the humidifier water but also on the

adherence to the exchange intervals of the upstream air filter, the air velocity and the micro-biological

and chemical composition of the supply air. Therefore the service intervals must be determined for each

system separately.

The interval time for a complete system service is to be determined at commissioning. A typical interval

time is

2000 hours of operation.

Depending on the encountered hygiene status when performing a complete system service the interval

time must be decreased or increased.

In any case the Nortec ME Direct Feed should receive a complete service at least once annually.

Note: We recommend to perform a minor service between two complete system service.

5.3

Maintenance guide

The Nortec ME unit will form part or your hot and cold water system and as such require you to undertake

certain duties with regards to local regulations and bylaws concerning the control of Legionella microbes

in water systems. Your water sampling / testing and disinfection regime must be based on results of a

site specific risk assessment.

If any further assistance is required or you are interested in a planned maintenance quote, please contact

your Nortec distributor

.

Note: routine water sampling and testing is not included as part of a Nortec service contract.

Please note that the information given in the table below is only to act as a guide which shows the work

to be carried out on “Minor Service” and “Complete System Service”.

Correct maintenance is vital to ensure optimum output, reliability and safety.

Operations

Minor

Service

Complete

System Service

Replace inlet water filter if applicable

Yes

Yes

Check all solenoid valves

Yes

Yes

Clean all solenoid valves

–––

Yes

Replace purge valve flow restrictor (if applicable)

–––

Yes

Check all hoses and connectors

Yes

Yes

Check flow restrictors in hydraulic manifold

–––

Yes

Clean inlet valve strainer

–––

Yes

Replace all feed hose

–––

Yes

Check distribution headers

Yes

Yes

Clean distribution headers

–––

Yes

Clean front section of tank

Yes

Yes

Check droplet separator (if applicable) and evaporator cassettes in suit-

able condition

Yes

Yes