Fault elimination

6

Fault elimination

Important! Most operational malfunctions are not caused by faulty equipment but rather by improper

installation or disregarding of planning guidelines. Therefore, a complete fault diagnosis always involves

a thorough examination of the entire system. Often, the installations have not been properly executed,

or the fault lies with the humidity control system.

6.1

Malfunction list

Malfunction

Cause

Remedy

Residual water in the section

of the duct downstream of the

evaporative module.

Face velocity is too high. Systems

without droplet separator max

3.5 m/s (689 fpm), systems with

a droplet separator max. 4.5 m/s

(886 fpm).

Install droplet separator or reduce air

velocity in the duct.

Water tank, water piping or hydraulic

manifold is leaking.

Check/seal water tank, water piping

and hydraulic manifold.

Water flow to media too high.

Check/replace flow restrictors in the

hydraulic manifold.

Evaporative cassettes have become

blocked with minerals.

Check set up, replace evaporative

cassettes, perform system service.

Uneven or non laminar air flow.

Check design conditions of AHU.

Install perforated plate on the air

supply side.

Air on temperature is too low.

Check design conditions of AHU. and

increase temperature.

Humidity/cooling demand

present however the Nortec ME

Direct Feed does not humidify.

Shut-off valve in the water supply

line closed.

Open shut-off valve.

Site control are not correct.

Prove controls and control module.

Maximum humidification/cooling

capacity is not reached.

Insufficient water supply capacity.

Check water supply, increase water

pressure.

Evaporative cassettes have become

blocked with minerals.

Check set up, replace evaporative

cassettes, perform system service.