Nortec Air Humidification System BS User Manual

Page 17

Advertising
background image

25.05.05-A

page 17 of 30

NOTE:
If the water hardness is higher then 20°dH (German hardness) it is recommended to use a water
softener. Please contact the Nortec sales man if you have questions.

4.3.2

Requirements regarding water treatment

The operator shall ensure that the following requirements are met on a permanent basis.

-

A three-stage water treatment system has to be used

-

Water softening (<0.1 °dH at the outlet)

-

Filtering (mechanical filter 5u + activated-carbon filter)

-

Demineralisation by reverse osmosis (inorganic membrane)

-

Water values at the outlet of the water treatment system

Î

Water hardness

< 0.1 °dH

Î

Conductivity

5-10 µS

Î

Water temperature

6-25 °C (43-77°F)

Î

Flow pressure

2-3 bar (43-58psi)

-

The product has to be conducted in a closed system up to point where it exits the
nozzle and it may not get in contact with the air in the room any time.

-

No water tanks with float control may be used. Closed membrane tanks made of stainless steel or
plastic have to be used for intermediate storage of the product (pressure control) instead.

-

Fittings and tubes have to be made of materials authorised for the food industry (plastic, stainless
steel). Do not use copper or brass tubes!

-

The treated water has to be free from organic substances.

4.4

Notes on compressed air supply


The operator shall ensure that the following requirements are met on a permanent basis.

-

The compressed air must have respiratory air quality and be free from contamination
(residual oil content < 0.003 mg/m

3

, dust, water, etc.).

-

The admissible inlet pressure on the wall brackets is max. 6 bar (without pressure
fluctuations and pressure blows).

-

When dimensioning the compressor and/or the outlet pressure, possible losses via the tube
network have to be taken into consideration.

-

It is recommended to install a micro filter and an activated carbon filter.

-

When an manometer and a pressure-relief device are installed in the compressed air feed, the
performance of the system can be assessed more easily.

-

Important! The compressed air line has to be blown out before it is connected.