Vav/cav controller technical guide 11, Space humidity sensor, Fan proof of flow switch – Orion System MUA II Controller User Manual

Page 11: Outside air humidity sensor, Figure 12: humidity, Sensor wiring, Figure 13: space humidity sensor wiring, Figure 14: fan proof of flow switch wiring

Advertising
background image

VAV/CAV Controller

Technical Guide

11

Figure 12: Humidity

Sensor Wiring

GND

INPUTS

GND

AOUT1
AOUT2

GND

+VDC

AIN1
AIN2
AIN3
AIN4
AIN5

AIN7

MUA II Controller Board

250 Ohm

Resistor

(Shipped With Sensor)

To be Installed Between

AIN7 and GND

The Pull-up Resistor (PU7)
Must Be Removed
When Using A 4-20ma Device

If You Are Using The Standard Factory Supplied Humidity Sensor, It Has
Terminals Labeled “+ (T1)” And - (T2)”. Terminal + (T1)” Is The Voltage
Input And Should Be Connected To The Terminal Labeled +VDC On The
MUA II Controller. Terminal “- (T2)” Is The 4-20 Ma Output Signal And
Should Be Connected To The Terminal Labeled AIN7 On The MUA II
Controller.

If A

Sensor Other Than The One Supplied By The Factory Is Used, Refer To
The Wiring Instructions Shipped With The Sensor.

A Factory Supplied 250 Ohm Resistor Should Be Connected

Between AIN 7 And A Ground Terminal On The MUA II Controller.

+ (T1)

- (T2)

Figure 13: Space Humidity Sensor Wiring

Space Humidity Sensor

A Space Humidity Sensor or a Fan Proof Of Flow Switch can be con-
nected to AIN7 on the MUA II controller. Shown below is the Space
Humidity Sensor wiring.

Fan Proof Of Flow Switch

If a Fan Proof Of Flow Switch is required then obviously the Space
Humidity Sensor option is not available. By the same token if a Space
Humidity Sensor is required then the Fan Proof Of Flow Switch option
is not available. See Fan Proof Of Flow Switch wiring below.

GND

INPUTS

GND

AOUT1
AOUT2

GND

+VDC

AIN1
AIN2
AIN3
AIN4
AIN5

AIN7

Outdoor

Air Humidity

Sensor - 4-20mA

Seal All Conduit Fittings
With Silicone Sealant.

MUA II Controller Board

250 Ohm

Resistor

(Shipped With Sensor)

To be Installed Between

AIN5 and GND

The Pull-up Resistor (PU5)
Must Be Removed
When Using A 4-20ma Device

If You Are Using The Standard Factory Supplied Humidity Sensor, It
Has Terminals Labeled “H+ (T1)” And “H- (T4)”. Terminal “H+ (T1)” Is
The Voltage Input And Should Be Connected To The Terminal Labeled
+VDC On The VAV/CAV Controller. Terminal “H- (T4)” Is The 4-20 Ma
Output Signal And Should Be Connected To The Terminal Labeled AIN
5 On The VAV/CAV Controller.

If A Sensor Other Than The One Supplied By The

Factory Is Used, Refer To The Wiring Instructions Shipped With The
Sensor.

A Factory Supplied 250 Ohm Resistor

Should Be Connected Between AIN 5 And A Ground Terminal On The
VAV/CAV Controller.

H-(T4)

H+(T1)

Outside Air Humidity Sensor

If you want to install a humidity sensor onto the MUA II controller, it
is important that you follow these instructions. There are 2 terminals
labeled “H+” and “H-”. Terminal “H+” will connect to the connection
labeled “+VDC” on the analog input block. See Figure 12. Terminal
“H-” connects to the connection labeled “AIN 5” on the analog input
block. Also the resistor labeled “PU5” needs to be removed. Lastly, a

supplied 250 Ohm, 1/4 Watt, 1% resistor needs to be installed between
“AIN 5” and “GND”. See Figure 12 for detailed wiring.

Warning: It is very important to be certain that all wiring is

correct as shown in the wiring diagram below.
Failure to observe the correct polarity will result in
damage to the Humidity Sensor or controller.

GND

INPUTS

GND

AOUT1
AOUT2

GND

+VDC

AIN1
AIN2
AIN3
AIN4
AIN5

AIN7

MUA II Controller Board

Fan Proof Of Flow

Switch

Figure 14: Fan Proof Of Flow Switch Wiring

Advertising