Two condenser head pressure module, Stand-alone wiring, Technical guide 10 – Orion System Two Condenser Head Pressure Module User Manual

Page 10: Condenser type selection, Condenser fan a ecm motor, Condenser fan b ecm motor, Condenser signal b, Condenser signal a

Advertising
background image

Two Condenser Head Pressure Module

Technical Guide

10

Stand-Alone Wiring

Stand-Alone Wiring

To operate the Two Condenser Head Pressure Module as Stand Alone,
connect the Module to a 24 VAC connection with an appropriate VA
rating. See Figure 6 for wiring.

Check all wiring leads at the terminal block for tightness. Be sure that
wire strands do not stick out and touch adjacent terminals. Confi rm that
all transducers required for your system are mounted in the appropriate
location and wired into the correct terminals.

Figure 6: Two Condenser Head Pressure Module as Stand-Alone

SIG

GND

+V

BK

RD
WH

24 VAC Transformer

3 VA Minimum

Line Voltage

24 V

A

C

GND

WARNING!!
Observe Polarity! All boards
must be wired with GND-to-GND
and 24 VAC-to-24 VAC. Failure
to observe polarity could result in
damage to the boards.

OE370-23-HP2C-C

Two Condenser Head Pressure Module

+5V

SIG 2

GND

OP

T

IO

N

S

ALARM

ANALOG

STAT

+5V

COMM

GND

SIG 4

GND

BIN 2

R1

R2

GND

RELAYS

ADDRESS

SIG 3

+5V

GND

BIN 1

COM

+5V

SIG 1

R3

R4

Rc

AO1

AO2

PWM1-

PWM1+

PWM2-

PWM2+

SIG

GND

+V

BK

RD
WH

SIG

GND

+V

BK

RD
WH

SIG

GND

+V

BK

RD
WH

Head Pressure Transducers

0 - 667 PSI

(One Per Refrigerant Circuit)

PWR

OPTIONS Dip Switch is

Used for Setting the Head

Pressure Setpoint if Not

Using Default Setpoint.

COM

Condenser Fan A

ECM Motor

+

COM

Condenser Fan B

ECM Motor

+

COM

+

Condenser

Signal B

COM

+

Condenser

Signal A

CONDENSER A ENABLE

R1

HVAC UNIT CONNECTION

R3

CONDENSER B ENABLE

NOTE:

NORMALLY OPEN AND

RATED FOR 24 VAC POWER
ONLY

ALL RELAY OUTPUTS

ARE

- 1 AMP MAXIMUM LOAD

COMM

Set ADDRESS Dip Switch 1 to ON

for Water Cooled or to OFF for Air

Cooled. Currently showing OFF for

Air Cooled.

Set ADDRESS Dip Switch 3 to ON

to disable Circuit B alarms when

only one Condenser is Used.

Currently showing OFF.

ADDRESS Dip Switch 4 should

always be set to ON to make

reversing valve "ON to Cool / OFF

to Heat". Currently showing ON.

CONDENSER ON/OFF (Y1 CALL)

COOLING ENABLE (O CALL)

COM

LED BLINK CODES

LED NAME

STAT

BLINKS QTY. OF SENSORS INSTALLED

LED NAME

ALARM

NO PROBLEMS

0

NO SENSORS DETECTED

1

HIGH HEAD PRESSURE DETECTED

2

LOW HEAD PRESSURE DETECTED

3

WattMaster Label

Rev.: 1H

#LB102081

E-BUS

Connector

E-BUS

Connector

+5V

SIG 1

GND

+5V

SIG 2

GND

+5V

SIG 3

GND

+5V

SIG 4

GND

+24

VAC

GND

BIN 1

BIN 2

COM

HEAD
PRESSURE
TRANSDUCER #1

HEAD
PRESSURE
TRANSDUCER #2

HEAD
PRESSURE
TRANSDUCER #3

HEAD
PRESSURE
TRANSDUCER #4

COMMON

PWM2+

Two Condenser Head Pressure Module

2C

Orion No.:OE370-23-HP

AAON Coil No.:

30310

Circuit A1

Circuit A2

Circuit B1

Circuit B2

www.aaon.com

AO1

AO2

GND

COND. A & B ENABLE

COOL ENABLE

RELA

Y

C

ONT

A

CT

RA

TING

IS

1

A

MP

MAX

@

24

V

A

C

COND. A ENABLE

COND. B ENABLE

COND. A SIGNAL
COND. B SIGNAL

COOL ENABLE

COOL ENABLE

PWM1-

PWM1+

PWM2-

COND. FAN A

COND. FAN B

COND. FAN A

COND. FAN B

GND

R1

R2

R3

R4

RC

RELAY COMMON

Condenser Type Selection

As shown in Figure 6, set ADDRESS dip switch 1 to ON for water
cooled or to OFF for air cooled. Refer to page 11 for further instructions.

Revised 7/26/11