Two condenser head pressure module, Appendix for version 1.04 and earlier, Technical guide – Orion System Two Condenser Head Pressure Module User Manual

Page 21: Stand-alone wiring, Condenser fan a ecm motor, Condenser fan b ecm motor, Condenser signal b, Condenser signal a

Advertising
background image

Technical Guide

Two Condenser Head Pressure Module

21

Appendix for Version 1.04 and Earlier

SIG

GND

+V

BK

RD
WH

24 VAC Transformer

3 VA Minimum

Line Voltage

24 V

A

C

GND

WARNING!!
Observe Polarity! All boards
must be wired with GND-to-GND
and 24 VAC-to-24 VAC. Failure
to observe polarity could result in
damage to the boards.

OE370-23-HP2C-C

Two Condenser Head Pressure Module

+5V

SIG 2

GND

OP

T

IO

N

S

ALARM

ANALOG

STAT

+5V

COMM

GND

SIG 4

GND

BIN 2

R1

R2

GND

RELAYS

ADDRESS

SIG 3

+5V

GND

BIN 1

COM

+5V

SIG 1

R3

R4

Rc

AO1

AO2

PWM1-

PWM1+

PWM2-

PWM2+

SIG

GND

+V

BK

RD
WH

SIG

GND

+V

BK

RD
WH

SIG

GND

+V

BK

RD
WH

Head Pressure Transducers

0 - 667 PSI

(One Per Refrigerant Circuit)

PWR

OPTIONS Dip Switch is

Used for Setting the Head

Pressure Setpoint if Not

Using Default Setpoint.

COM

Condenser Fan A

ECM Motor

+

COM

Condenser Fan B

ECM Motor

+

COM

+

Condenser

Signal B

COM

+

Condenser

Signal A

CONDENSER A ENABLE

R1

HVAC UNIT CONNECTION

R3

CONDENSER B ENABLE

NOTE:

NORMALLY OPEN AND

RATED FOR 24 VAC POWER
ONLY

ALL RELAY OUTPUTS

ARE

- 1 AMP MAXIMUM LOAD

COMM

Set ADDRESS Dip Switch 1 to ON

for Water Cooled or to OFF for Air

Cooled. Currently showing OFF for

Air Cooled.

Set ADDRESS Dip Switch 2 to OFF

for R410-A Refrigerant or to ON for

R22 Refrigerant. Currently showing

OFF for R410-A Refrigerant.

Set ADDRESS Dip Switch 3 to ON

to disable Circuit B alarms when

only one Condenser is Used.

Currently showing OFF.

ADDRESS Dip Switch 4 should

always be set to ON to make

reversing valve "ON to Cool / OFF

to Heat". Currently showing ON.

CONDENSER ON/OFF (Y1 CALL)

COOLING ENABLE (O CALL)

COM

LED BLINK CODES

LED NAME

STAT

BLINKS QTY. OF SENSORS INSTALLED

LED NAME

ALARM

NO PROBLEMS

0

NO SENSORS DETECTED

1

HIGH HEAD PRESSURE DETECTED

2

LOW HEAD PRESSURE DETECTED

3

WattMaster Label

Rev.: 1H

#LB102081

E-BUS

Connector

E-BUS

Connector

+5V

SIG 1

GND

+5V

SIG 2

GND

+5V

SIG 3

GND

+5V

SIG 4

GND

+24

VAC

GND

BIN 1

BIN 2

COM

HEAD
PRESSURE
TRANSDUCER #1

HEAD
PRESSURE
TRANSDUCER #2

HEAD
PRESSURE
TRANSDUCER #3

HEAD
PRESSURE
TRANSDUCER #4

COMMON

PWM2+

Two Condenser Head Pressure Module

2C

Orion No.:OE370-23-HP

AAON Coil No.:

30310

Circuit A1

Circuit A2

Circuit B1

Circuit B2

www.aaon.com

AO1

AO2

GND

COND. A & B ENABLE

COOL ENABLE

RELA

Y

C

ONT

A

CT

RA

TING

IS

1

A

MP

MAX

@

24

V

A

C

COND. A ENABLE

COND. B ENABLE

COND. A SIGNAL
COND. B SIGNAL

COOL ENABLE

COOL ENABLE

PWM1-

PWM1+

PWM2-

COND. FAN A

COND. FAN B

COND. FAN A

COND. FAN B

GND

R1

R2

R3

R4

RC

RELAY COMMON

Figure 10: Version 1.04 and Earlier One Condenser Head Pressure Module Wiring Diagram (Stand-Alone)

Stand-Alone Wiring

Versions 1.01 through 1.04 utilize Dipswitch 2 in stand-alone mode
for refrigeration selection. See Tables 10 & 11 for further information.