Two condenser head pressure module, Technical guide – Orion System Two Condenser Head Pressure Module User Manual

Page 7

Advertising
background image

Technical Guide

Two Condenser Head Pressure Module

7

If using a spliced terminal connection for longer runs, one module can be
connected to the E-BUS Distribution Module and any additional modules
would be daisy-chained to the fi rst module. For more information, refer
to the E-BUS Distribution Module Technical Guide.

NOTE: Contact Factory for the correct HSSC cable length for

your application. Cables are available in ¼, ½, 1, 2, 3,
4, and 5 Meter lengths and 100 and 150 Foot lengths.

WARNING!!
Observe Polarity! All
boards must be wired with
GND-to-GND and 24 VAC-
to-24 VAC. Failure to
observe polarity could
result in damage to the
boards.

OE365-23-EBD E-BUS

Distribution Module

GND

-COMM

SHLD

+COMM

INPUT

+COMM

SHLD

-COMM

GND

+VDC

485 DRV

24VAC

GND

PWR

YS102308
REV 1
I2C TO COMM
DIST. BOARD

OUTPUT

Modular Cable

Connect To

VCM-X WSHP or

VCM-X Modular Controller,

HSSC Cable

Connect To E-BUS

Distribution Module

SIG

GND

+V

BK

RD
WH

SIG

GND

+V

BK

RD
WH

SIG

GND

+V

BK

RD
WH

SIG

GND

+V

BK

RD
WH

COM

Condenser Fan A

ECM Motor

+

Head Pressure Transducers

0 - 667 PSI

(One Per Refrigerant Circuit)

OE370-23-HP2C-C

Two Condenser Head Pressure Module

OPTIONS Dip Switch Setting Not

Required When Connected To

VCM-X Modular, VCM-X WSHP

or SA Controller

+5V

SIG 2

GND

OP

T

IO

N

S

ALARM

ANALOG

STAT

+5V

COMM

GND

SIG 4

GND

BIN 2

R1

R2

GND

RELAYS

ADDRESS

SIG 3

+5V

GND

BIN 1

COM

+5V

SIG 1

R3

R4

Rc

AO1

AO2

PWM1-

PWM1+

PWM2-

PWM2+

Set ADDRESS Dip

Switch 1 to ON for

Water Cooled or to

OFF for Air Cooled.

Currently showing

OFF for Air Cooled.

If Using (2)

Modules, Set

ADDRESS Dip

Switch 2 to OFF for
Address 1 or to ON

for Address 2.

ADDRESS Dip

Switch 4 should

always be set to

ON to make

reversing valve "ON

to Cool / OFF to
Heat". Currently

showing ON.

Set

to OFF if Using (1)

Module. Currently

showing OFF.

Set ADDRESS Dip

Switch 3 to ON to

disable Circuit B

alarms when only
one Condenser is

Used. Currently

showing OFF.

PWR

COM

Condenser Fan B

ECM Motor

+

COM

+

Condenser

Signal B

COM

+

Condenser

Signal A

Connect To Other

WattMaster-Approved

E-BUS Expansion Module(s)

HSSC Cable

24 VAC Transformer

3 VA Minimum

Line Voltage

24 V

A

C

GND

WARNING!! Observe Polarity! All
boards must be wired with GND-to-
GND and 24 VAC-to-24 VAC.
Failure to observe polarity could
result in damage to the boards.

CONDENSER A ENABLE

R1

HVAC UNIT CONNECTION

R3

CONDENSER B ENABLE

NOTE:

NORMALLY OPEN AND

RATED FOR 24 VAC POWER
ONLY - 1 AMP MAXIMUM LOAD

ALL RELAY OUTPUTS

ARE

COMM

LED BLINK CODES

LED NAME

STAT

BLINKS QTY. OF SENSORS INSTALLED

LED NAME

ALARM

NO PROBLEMS

0

NO SENSORS DETECTED

1

HIGH HEAD PRESSURE DETECTED

2

LOW HEAD PRESSURE DETECTED

3

WattMaster Label

Rev.: 1H

#LB102081

E-BUS

Connector

E-BUS

Connector

+5V

SIG 1

GND

+5V

SIG 2

GND

+5V

SIG 3

GND

+5V

SIG 4

GND

+24

VAC

GND

BIN 1

BIN 2

COM

HEAD
PRESSURE
TRANSDUCER #1

HEAD
PRESSURE
TRANSDUCER #2

HEAD
PRESSURE
TRANSDUCER #3

HEAD
PRESSURE
TRANSDUCER #4

COMMON

PWM2+

Two Condenser Head Pressure Module

2C

Orion No.:OE370-23-HP

AAON Coil No.:

30310

Circuit A1

Circuit A2

Circuit B1

Circuit B2

www.aaon.com

AO1

AO2

GND

COND. A & B ENABLE
COOL ENABLE

RELA

Y

C

ONT

A

CT

RA

TING

IS

1

A

MP

MAX

@

24

V

A

C

COND. A ENABLE

COND. B ENABLE

COND. A SIGNAL
COND. B SIGNAL

COOL ENABLE

COOL ENABLE

PWM1-

PWM1+

PWM2-

COND. FAN A

COND. FAN B

COND. FAN A

COND. FAN B

GND

R1

R2

R3

R4

RC

RELAY COMMON

WARNING: Be sure all controllers and modules are

powered down before connecting or

disconnecting HSSC cables.

VCM-X Controller to Two Condenser Head Pressure Module Wiring

Figure 4, cont.: VCM-X WSHP Controller to Two Condenser Head Pressure Module Wiring Diagram