Two condenser head pressure module, Technical guide 6 – Orion System Two Condenser Head Pressure Module User Manual

Page 6

Advertising
background image

Two Condenser Head Pressure Module

Technical Guide

6

VCM-X Controller to Two Condenser Head Pressure Module Wiring

VCM-X Modular or VCM-X WSHP

Controller to Two Condenser Head

Pressure Module Wiring

Up to (2) Two Condenser Head Pressure Modules can be daisy-chained
together and connected to the E-BUS Distribution Module using a modu-
lar HSSC cable. The Two Condenser Head Pressure Module requires a
24 VAC power connection with an appropriate VA rating.

Figure 4: VCM-X WSHP Controller to Two Condenser Head Pressure Module Wiring Diagram

Connect To

E-BUS

Distribution

Module

Line Voltage

24 VAC

GND

Line Voltage

All Comm Loop Wiring Is

Straight Thru

24VAC

GND

Local Loop

RS-485

9600 Baud

See Individual Component

Wiring Diagrams For

Detailed Wiring Of Analog

Inputs And Outputs

For Stand Alone Applications,
Connect To System Manager.

For Network Applications

Connect To Next Controller

And/Or MiniLink PD On Local Loop.

G - Fan ON/OFF Only

R - 24VAC

Relay Output Contacts
R2 Through R5 May Be User-Configured
For The Following:
1 - Heating Stages
2 - See Note 1 Below
3 - Warm-up Mode Command (VAV Boxes)
4 - Reversing Valve (Air To Air Heat Pumps)
5 - Reheat Control (Dehumidification)
6 - Exhaust Fan Interlock
7 - Preheater For Low Ambient Protection
8 - Alarm
9 - Override
10 - Occupied
11 - OA Damper
12 - Heat Wheel
13 - Emergency Heat
Note: 1.) When Using the HP2C Module,
All Compressors Will Be Wired From the
Protection Module, Not the VCM-X
Controller.
2.) A Total Of 20 Relays Are Available By
Adding Relay Expansion Modules. All
Expansion Module Relay Outputs Are User-
Configurable As Listed Above.

Connect FRP Tubing To High Pressure
Port (Bottom Tube) and Route To Static
Pressure Pickup Probe Located In Unit
Discharge. Leave Port Marked “Lo” Open
To Atmosphere

OE271

Static Pressure

Transducer

Splice If Required

Connect To E-BUS Distribution Module
or Expansion Module(s) (When Used)

Connect To Digital Room Sensor And/Or
Digital CO Sensor

2

Warning:
24 VAC Must Be Connected So That All Ground
Wires Remain Common. Failure To Do So Will
Result In Damage To The Controllers.

T to T, R to R & SHLD to SHLD

Size Transformer For Correct
Total Load.
VCM-X Controller = 8 VA

OE332-23-VCMX-WSHP

VCM-X WSHP Controller

Note:
All Relay Outputs Are Normally Open And Rated
For 24 VAC Power Only.
1 Amp Maximum Load.

AI1

AI1 SET

AI2 SET

AI3 SET

AI4 SET

AI5 SET

AI7 SET

AI2

AI3

AI4

AI5

AI7

AI1 SET

AI2 SET

AI3 SET

AI4 SET

AI5 SET

AI7 SET

Jumpers

The E-BUS Distribution Module connects to the VCM-X Modular
Controller, VCM-X WSHP Controller, VCM-X Expansion Module,
or 12 Relay Expansion Module using the I

2

C port. See Figure 4 below

for wiring.

Any E-BUS Module can be connected to each of the four E-BUS

Dis-

tribution Module’s output ports or can be daisy-chained together using
HSSC cables.