Troubleshooting for Stand Alone Mode

If you suspect or encounter general problems during operation of the
Two Condenser Head Pressure Module while in Stand Alone Mode,
follow the Troubleshooting Flowchart in Figure 7 below.

Troubleshooting

Is “ERROR”

LED Blinking ?

Note: “STAT” LED

will blink the # of

Good sensors

connected

No

Is

“STAT” LED

blinking correct

Sensors?

Check wiring

on all sensors

Measure DC

Volts between

SIGx & GND for

All sensors .

Compare readings

to chart

.

No

Enable

Inputs

?

BIN 2

Yes

Yes

Pressure is ??

than Setpoint ?

No

Monitor DC

Volts on A ut 1

O

A ut

Voltage

O

1 & 2

Should Modulate

Up to a Max

Voltage of 10VDC

(See Sequence)

Higher

Monitor DC

Volts on

A ut 1 & 2 Voltage

O

should Modulate

Down to a Min

voltage of 0VDC

(See Sequence)

Lower

There will

be No

Change on

A ut 1

O

& 2

Same

1 Blink =

None of the

Sensors are

Check wiring

on all sensors

Measure DC

Volts between

SIGx & GND for

all sensors

Compare readings

to chart

Yes

2 Blinks =High

Pressure on one

of the Sensors

(More than

600 PSI)

3 Blinks =

Lo Pressure

the Sensors

Less than 35 PSI

Check

Refrigerant
Charge on
All Circuits

Head Pressure Control

Troubleshooting Flowchart

(Stand Alone Mode)

Start Here

Is

Blinking?

No

Is

“ERROR”

LED Blinking?

No

Is There

24VAC

@

“PWR”

Testpoint?

No

Verify

Incoming

Power

No

Yes

Yes

Yes

Yes

“STAT” LED

Are

Heat

# of

Detected

Check

Refrigerant
Charge on
All Circuits

On one of

Active

& A ut 2

O

A ut 1 & 2

O

A & B

Call AAON

Technical

Support

Call AAON

Technical

Support

Call WattMaster

Technical

Support

Is

A or B Fan or

Condenser

Water Valve

Operating?

Fan Speed

Be at 100%

or Water Valve

Position Will