0) instructions for pressure test gauge connection – Space Ray LTU Series Two Stage User Manual

Page 16

Advertising
background image

Form #42710010

-14-

May 2013

12.0)

INSTRUCTIONS FOR PRESSURE TEST GAUGE CONNECTION

SUPPLY PRESSURE

SUPPLY PRESSURE

SUPPLY PRESSURE

SUPPLY PRESSURE
1. The installer will provide a 1/8” N.P.T. tapped plug, accessible for test gauge connection immediately

upstream of the gas supply connection to the heater.

MANIFOLD PRESSURE

MANIFOLD PRESSURE

MANIFOLD PRESSURE

MANIFOLD PRESSURE –

– COMBINATION GAS VALVE IS FACTORY SET

COMBINATION GAS VALVE IS FACTORY SET

COMBINATION GAS VALVE IS FACTORY SET

COMBINATION GAS VALVE IS FACTORY SET

1. Turn the gas valve to the “OFF” position. Remove the 1/8” plug from the combination gas valve at the

Outlet Pressure T

Outlet Pressure T

Outlet Pressure T

Outlet Pressure Tap

ap

ap

ap below and connect a 1/8” nipple to the tapped hole. Connect the test gauge to the

nipple. Turn on the gas supply.

2. With the main burner operating, check the burner manifold pressure using a water column manometer.

Gauges that measure pressure in pounds per square inch are not accurate enough to measure or set the
manifold pressure. All measurements MUST BE

MUST BE

MUST BE

MUST BE made when this heater and all other gas burning equipment

that is connected to the gas supply system are operating at maximum capacity.

3. The combination gas valve is factory set an

The combination gas valve is factory set an

The combination gas valve is factory set an

The combination gas valve is factory set and should not require adjustment.

d should not require adjustment.

d should not require adjustment.

d should not require adjustment. If full rate adjustment is

required, remove the cover screw. Using a small screwdriver, turn the adjustment screw clockwise

to

increase or counterclockwise to decrease the gas pressure to the burner. Replace the cover screw. NOTE:

NOTE:

NOTE:

NOTE:

The step opening pressure of this gas valve is not adjustable.

The step opening pressure of this gas valve is not adjustable.

The step opening pressure of this gas valve is not adjustable.

The step opening pressure of this gas valve is not adjustable.

4. Check the burner at step pressure, observing burner ignition and flame characteristics. The burner should

ignite properly and without flashback to the orifice, and should remain lit.

GAS PRESSURE TABLE

GAS PRESSURE TABLE

GAS PRESSURE TABLE

GAS PRESSURE TABLE

GAS TYPE

GAS TYPE

GAS TYPE

GAS TYPE

MANIFOLD PRESSURE

MANIFOLD PRESSURE

MANIFOLD PRESSURE

MANIFOLD PRESSURE

SUPPLY PRESSURE

SUPPLY PRESSURE

SUPPLY PRESSURE

SUPPLY PRESSURE

High

High

High

High

Low

Low

Low

Low

Minimum*

Minimum*

Minimum*

Minimum*

Maximum

Maximum

Maximum

Maximum

Natural Gas

3.5” W.C.

1.4” W.C.

5” W.C.

14” W.C.

Propane Gas

10.0” W.C.

4.0” W.C.

11” W.C.

14” W.C.

* Minimum permissible gas supply pressure for purpose of input adjustment.