0) venting – Space Ray LTU Series Two Stage User Manual

Page 21

Advertising
background image

Form #42710010
May 2013

-19-

14.0)

VENTING

Failure to do so may result in death, serious injury, property damage or illness

from Carbon Monoxide poisoning.

Heaters installed in an unvented mode require a minimum ventilation flow of

4 CFM per 1,000 Btu/hr of total installed capacity.
In buildings with airborne contamination the heater must be installed with

fresh air for combustion.

CARBON MONOXIDE HAZARD

A.

A.

A.

A.

BASIC FLUE VENTING

BASIC FLUE VENTING

BASIC FLUE VENTING

BASIC FLUE VENTING — Venting must comply with the latest edition of the National Fuel Gas Code (ANSI
Z223.1-latest edition) or the authority having jurisdiction. Other venting references are in the equipment
volume of the ASHRAE Handbook.

SINGLE HEATER VENTING (VERTICAL THROUGH THE ROOF)

SINGLE HEATER VENTING (VERTICAL THROUGH THE ROOF)

SINGLE HEATER VENTING (VERTICAL THROUGH THE ROOF)

SINGLE HEATER VENTING (VERTICAL THROUGH THE ROOF)
1. When venting the heater to outside of building through a roof, use single-wall metal pipe. This is to be

constructed of galvanized sheet metal or other approved noncombustible corrosion-resistant material as
allowed by state or local codes.

2. A vent passing through a combustible roof shall extend through an approved clearance roof thimble.

Double-wall, Type B vent must be used for the portion of the vent system which passes through the
combustible roof. An approved vent cap must be attached to end of the flue.

3. The maximum equivalent length of vent pipe should be carefully observed. A safety switch in the heater is

designed to shut the heater off before excessive flue restriction causes bad combustion. Refer to the Vent
Sizing Table for maximum vent lengths and vent pipe diameter.

Minimum Equivalent Length = 5 ft. of pipe

Maximum Equivalent Length = 75 ft. of pipe

Use the following correction factors to obtain the equivalent length:

Subtract 15 ft. if the run is horizontal.

Subtract 10 ft. for an approved vent cap.

Subtract 10 ft.for each elbow beyond 15 ft. from the heater.

Subtract 15 ft. for each elbow within 15 ft. of the heater.

4. Joints between sections of piping shall be fastened by sheet metal screws or other approved means and

should be sealed to prevent leakage of flue gas into building. Aluminum or Teflon tape suitable for 550ºF
(3M Company tapes 433 or 363) or silicone sealant is recommended.

5. Avoid locating elbows in the first 5’ of vent pipe whenever possible. Limit to (2) 90° elbows. When vent pipe

is in a horizontal run, it must have 1/4 inch per foot rise.

6. All portions of the vent pipe shall be supported to prevent from sagging (6’ spacing is recommended).

7. When the vent pipe passes through areas where the ambient temperature is likely to induce condensation

of the flue gases, the vent pipe should be insulated and a condensation drain should be provided.

8. Minimum clearance for single-wall flue pipe to combustible material shall be 6 inches. This may be reduced

when the combustible material is protected as specified in the National Fuel Gas Code or the authority
having jurisdiction.

9. Single-wall metal pipe shall not originate in any unoccupied attic or concealed space and shall not pass

through any attic, inside wall or concealed space, or through any floor. For the installation of a single-wall
metal pipe through an exterior combustible wall, refer to latest edition of the National Fuel Gas Code or the
authority having jurisdiction.

10. A venting system shall terminate at least 3 ft. above any forced air inlet located within 10 ft.

Model

Model

Model

Model

Heat

Heat

Heat

Heat

exchanger

exchanger

exchanger

exchanger

length ft

length ft

length ft

length ft

Maximum vent length ft. (4” diameter

Maximum vent length ft. (4” diameter

Maximum vent length ft. (4” diameter

Maximum vent length ft. (4” diameter))))

Maximum Fresh air

Maximum Fresh air

Maximum Fresh air

Maximum Fresh air

intake length ft

intake length ft

intake length ft

intake length ft

(4” diameter)

(4” diameter)

(4” diameter)

(4” diameter)

Vertical Venting

Vertical Venting

Vertical Venting

Vertical Venting

Sidewall Venting

Sidewall Venting

Sidewall Venting

Sidewall Venting

LTU 40

30

100

75

50

LTU 50

30

100

75

50

LTU 60

30

100

75

50

LTU 75

30

100

75

50

Advertising
This manual is related to the following products: