0) troubleshooting guide – Space Ray LTU Series Two Stage User Manual

Page 30

Advertising
background image

Form #42710010

-28-

May 2013

20.0)

TROUBLESHOOTING GUIDE

T

urn on line volt

age.

Does the green monitoring light come on in the control cabinet?

Y

es

No

Is there 120V between the L1 and L2 terminals on the terminal block in the control cabinet?

Y

es

No

Are the black lead wires of the green light securely on the terminals L1 and L2?

No

Y

es

Replace the green light.

Rep

air connection.

Check line volt

age

curcuit. Rep

air fault.

Adjust thermost

at to

the highest setting. Is the draf

t inducer

on?

Y

es

No

Is one lead wire of the draf

t inducer motor

securely on the terminal L2 in the control cabinet?

No

Y

es

Rep

air connection.

Is the other lead wire of the draf

t inducer

motor securely on the relay terminal 3 in the control cabinet?

Does the red monitoring light come on in the control cabinet?

Y

es

No

Rep

air connections.

Is the air hose securely connected to the air switch and the air sensing tubing at the draf

t inducer?

No

Clean out hose and probe.

T

roubleshooting

continued on the next page.

No

Y

es

Rep

air connection.

Disconnect the power and check motor lead wires.

Any wire

broken?

Y

es

No

Rep

air broken wires.

Check the blower wheel. Does it turn freely?

Y

es

Replace motor

Check blower wheel. Is there any damage?

Replace blower wheel.

Readjust blower wheel on shaf

t &

retighten set crew

.

Check the air sensing tube and hose.

Are

they clear and unobstructed?

Check the pressure at the air switch. Is it higher than the minimum required?

Rest

art

troubleshooting.

Is one red wire securely connecting relay terminal 5 and terminal C of the air switch in the control cabinet?

Y

es

Y

es

No

No

Y

es

No

Check the volt

age

between air switch terminal C and ground, is it 24 vac?

Y

es

Y

es

When the draf

t

inducer is running, is there 24 vac between air switch terminal NO and ground ?

No

Correct connection.

Is one lead wire of the red light securely connected to one transformer terminal along with two other white wires?

Correct connection.

Y

es

Y

es

No

Y

es

Y

es

Replace the air switch.

No

Check the air int

ake

and vent.

Are there

any blockages?

Y

es

No

Remove blockage. Rest

art

troubleshooting.

Is the other lead wire of the red light securely connected to terminal NO of the air switch along with a red wire from ignition module?

Is there 120V between terminal L2 and relay terminal 3?

No

Y

es

See sequence continued on the next page.

1

No

No

Correct connection.

No

See sequence continued on the next page.

2

Replace the red light.