INSTALLATION

Continued

INSTALLING DAMPER CLAMP
ACCESSORY FOR VENTED
OPERATION

Note:

When used as a vented decorative, appliance

must be installed only in a solid-fuel burning

fireplace with a working flue and constructed of

noncombustible material.

If your heater is a non-thermostatically-controlled

model, you may use this heater as a vented product.

There are three reasons for operating your heater

in the vented mode.

1. The fireplace does not meet the clearance

to combustibles requirements for vent-free

operation.

2. State or local codes do not permit vent-free

operation.

3. You prefer vented operation.

If reasons number 1 or 2 above apply to you, you

must permanently open chimney flue damper. You

must install the damper clamp accessory (to order,

see Accessories, page 26). This will insure vented

operation (see Figure 10). The damper clamp will

keep damper open. Installation instructions are

included with clamp accessory.

Figure 10 - Attaching Damper Clamp

Damper

Damper
Clamp

Damper

Manufactured

Fireplace

Masonry

Fireplace

Damper
Clamp

See chart below for minimum permanent flue

opening you must provide. Attach damper clamp

so the minimum permanent flue opening will be

maintained at all times.

INSTALLING REMOTE CONTROL
ACCESSORY BRACKET

If installing optional remote control accessory you

will need to install the remote accessory bracket

for the receiver.

Use screws provided to attach bracket to valve

bracket as shown in Figure 11.

Follow installation instructions included with

remote accessory.

Area of Various Standard Round Flues

Diameter

Area

5"
6"
"
8"

20 sq. inches
29 sq. inches
39 sq. inches
51 sq. inches

Chimney Height

Minimum Permanent

Flue Opening

6' to 15'

15' to 30'

39 sq. inches
29 sq. inches

Valve Bracket

Figure 11 - Attaching Remote Bracket to

Valve Bracket

Remote
Bracket

INSTALLING HEATER ASSEMBLY

WARNING: If installing in a

sunken fireplace, special care

is needed. You must raise the

fireplace floor to allow access

to heater control panel. This

will insure adequate air flow and

guard against sooting. Raise

fireplace floor with noncombus-

tible material. Make sure material

is secure.