Air for combustion and ventilation – Desa VFRMV18PB User Manual

Page 7

Advertising
background image

www.desatech.com

116412-01B



1. Determine the volume of the space (length x

width x height).

Length x Width x Height = _________cu. ft.

(volume of space)

Example: Space size 20 ft. (length) x 16 ft.

(width) x 8 ft. (ceiling height) = 2560 cu. ft.

(volume of space)

If additional ventilation to adjoining room is sup-

plied with grills or openings, add the volume of

these rooms to the total volume of the space.

2. Multiply the space volume by 20 to determine

the maximum Btu/Hr the space can support.

____________(volume of space) x 20 =

(Maximum Btu/Hr the space can support)

Example:

2560 cu. ft. (volume of space) x

20 = 51,200 (maximum Btu/Hr the space can

support)

3. Add the Btu/Hr of all fuel burning appliances

in the space.

Vent-free appliance

_________Btu/Hr

Gas water appliance*

_________Btu/Hr

Gas furnace

_________Btu/Hr

Vented gas appliance

_________Btu/Hr

Gas fireplace logs

_________Btu/Hr

Other gas appliances* +_________Btu/Hr

Total

=_________Btu/Hr

* Do not include direct-vent gas appliances.

Direct-vent draws combustion air from the

outdoors and vents to the outdoors.

Example:

Gas water appliance

_________Btu/Hr

Vent-free appliance

+_________Btu/Hr

Total

=_________Btu/Hr

4. Compare the maximum Btu/Hr the space can

support with the actual amount of Btu/Hr used.

___________ Btu/Hr (maximum the space

can support)

____________Btu/Hr (actual amount of

Btu/Hr used)

Example: 51,200 Btu/Hr (maximum the

space can support)

73,000 Btu/Hr (actual amount of

Btu/Hr used)

AIR FOR COMBUSTION

AND VENTILATION

Continued

The space in the previous example is a confined

space because the actual Btu/Hr used is more than

the maximum Btu/Hr the space can support. You

must provide additional fresh air. Your options

are as follows:

A. Rework worksheet, adding the space of an

adjoining room. If the extra space provides an

unconfined space, remove door to adjoining

room or add ventilation grills between rooms.

See Ventilation Air From Inside Building.

B. Vent room directly to the outdoors. See Ven-

tilation Air From Outdoors, page 8.

C. Install a lower Btu/Hr appliance, if lower

Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the

maximum Btu/Hr the space can support, the

space is an unconfined space. You will need

no additional fresh air ventilation.

WARNING: If the area in which

the appliance may be operated

is smaller than that defined as

an unconfined space or if the

building is of unusually tight

construction, provide adequate

combustion and ventilation air

by one of the methods described

in the National Fuel Gas Code,

ANSI Z223.1/NFPA 54 Section 5.3

or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining un-

confined space. When ventilating to an adjoining

unconfined space, you must provide two perma-

nent openings: one within 12" of the ceiling and

one within 12" of the floor on the wall connecting

the two spaces (see options 1 and 2, Figure 2 on

page 8). You can also remove door into adjoining

room (see option 3, Figure 2). Follow the National

Fuel Gas Code, ANSI Z223.1/NFPA 54, Section

5.3, Air for Combustion and Ventilation for re-

quired size of ventilation grills or ducts.

40,000

33,000

73,000

Advertising
This manual is related to the following products: