Wiring details, Technical guide mua ii controller 13 outside air, Temperature sensor – WattMaster MUA II User Manual

Page 13: Remote occupied contact

Advertising
background image

Technical Guide

MUA II Controller

13

Outside Air

Temperature Sensor

The Outside Air Sensor must be wired as shown in the illustration
below for proper operation. The Outside Air Temperature Sensor is a
10K Type III thermistor sensor. The sensor should be mounted in the
upright position as shown in an area that is protected from the elements
and direct sunlight. Be sure to make the wiring splices inside of the
Outside Air Temperature Sensor weathertight enclosure. See Figure
10
for detailed wiring.

Caution:

Be sure to mount the Outside Air Sensor in

an area that is not exposed to direct sunlight. A

shaded area under the eve of the building or

under the HVAC unit rainhood is normally a

good location. If the sensor is not located as

specifi ed, erroneous outside air temperature

readings will result. Unused conduit opening(s)

must have closure plugs installed and must be

coated with sealing compound to provide rain

tight seal. Water can damage sensor!

GND

INPUTS

GND

AOUT1
AOUT2

GND

+VDC

AIN1
AIN2
AIN3
AIN4
AIN5

AIN7

Outdoor

Air Temperature

Sensor

Make Splice Connections
Inside Sensor Enclosure
As Shown. Seal All
Conduit Fittings With
Silicone Sealant.

Mount Sensor Outdoors

In Shaded Protected

Area & In Upright

Position As Shown

Figure 10: Outside Air Temperature Sensor Wiring

GND

INPUTS

GND

AOUT1
AOUT2

GND

+VDC

AIN1
AIN2
AIN3
AIN4
AIN5

AIN7

MUA II Controller Board

Remote Occupied

Contact

(Relay By Others)

Figure 11: Remote Occupied Contact Wiring

Remote Occupied Contact

A Remote Occupied contact closure supplied from another Building
Automation System device can be used to enable Occupied and Unoc-
cupied modes on the MUA II Controller. This relay contact must be
a dry contact and be wired as shown below. See Figure 11 below for
detailed wiring.

Wiring Details

Advertising