Sequence of operations, Mua ii controller technical guide 20 – WattMaster MUA II User Manual

Page 20

Advertising
background image

MUA II Controller

Technical Guide

20

Temperature Protect

This mode occurs when the SAT rises above the High Cutoff Tempera-
ture Setpoint
or drops below the Low Cutoff Temperature Setpoint
for a defi ned period of time. To return to the normal mode, the SAT
must drop 10°F below the High Cutoff Temperature Setpoint or rise
10°F above the Low Cutoff Temperature Setpoint, depending on the
situation. See the table that follows:

Condition

Mode

SAT rises above the High Cutoff
Temperature

Heating & Cooling

Disabled

Blower Operation

for 3 Minutes

Then Off

SAT drops below the Low Cutoff
Temperature

After Temperature Protect is
initiated and SAT rises 10ºF above
the Low Cutoff Temperature

Return to Normal

Operation

After Temperature Protect is
initiated and SAT drops 10ºF below
the High Cutoff Temperature

Sequence of Operations

Heat

This mode occurs when the controller reads an OAT one Heating Dead-
Band
below the Supply Air Setpoint and a Dewpoint Temperature
below the Dewpoint Setpoint. The migration table for this mode is
shown below.

Condition

Mode

OAT rises above the Heat Setpoint

Vent Mode

Dewpoint Temperature rises above
the Dewpoint Setpoint

Dehumidifi cation

Figure 19: Heat Mode Staging

External Heating
This feature is designed to control an external Hot Water Valve or an
SCR Controller. Confi guring a relay for External Heating Control en-
ables this feature. This relay is activated any time the unit needs heat.
The output follows a proportional control scheme and can be confi g-
ured for a range of 0-10 VDC or 2-10 VDC. The External Heat relay is
deactivated when the call for heat or reheat is canceled or the Supply
Air Temperature
rises one Heating Deadband above the Supply Air
Temperature Setpoint.

Advertising