MUA II Controller

Technical Guide

16

Start-up & Commissioning

In order to have a trouble free start-up, it is important to follow a few
simple procedures. Before applying power for the fi rst time, it is very
important to correctly address the controller and run through a few
simple checks.

Controller Addressing

All MUA II Controllers are equipped with address switches. If the MUA
II Controller is to operate as a stand-alone system (not connected to any
other controllers), the controller address switch should be set for address
1. When using the Modular Service Tool or System Manager to program
and confi gure the MUA II Controller, you would enter this address to
communicate with the controller. When the system is to be connected to
other HVAC unit controllers on a communication loop, each controllers
address switch must be set with a unique address between 1 and 59. See
Figure 15 for address switch setting information.

4

NETWORK

TOKEN

16

32

8

SW1

ADD

2

1

ADDRESS

V6

POWER

GND

24VAC

L1

D16

R6

C9

SC1

R1

1

U1

1

D13

C16

VR2

TB4

R27

C13

R10

VR1

C19

C18

R7

D10

R13

D12

C7

CX10

U10

CX12

U12

U14

CX14

PJ3

PJ2

PJ1

EXPANSION

PRESSURE
SENSOR

C17

D15

R26

C20

R25

R24

R22

U15

CX13

U13

C15

R19

R15

C14

D18

D17

PU1

PU2

PU3

PU4

PU5

PU7

D6

D7

D8

D9

D11

D14

C12

C10

0-5

VDC

0-1

VDC

JP1

C1

1

X2

GND

TB3

INPUTS

GND

GND

+VDC

AIN1

AIN2

AIN3

AIN4

AIN5

AOUT1

AOUT2

AIN7

RN5

D19

CX15

16
32

TOKEN

NETWORK

8

4

2

1

Address Switch Shown Is

Set For Address 1

Address Switch Shown Is

Set For Address 13

Controller
Address Switch

This Switch Should Be
In The OFF Position
As Shown

Note:
The Power To The Controller Must Be Removed And
Reconnected After Changing The Address Switch Settings

Caution
Disconnect All Communication Loop Wiring From The
Controller Before Removing Power From The Controller.
Reconnect Power And Then Reconnect Communication Loop
Wiring.

ADDRESS

ADD

ADDRESS

ADD

ADDRESS

ADD

The Address For Each Controller

Must Be Unique To The Other Controllers

On The Local Loop And Be Between 1 and 59

Figure 15: MUA II Controller Address Switch Setting

Power Wiring

One of the most important checks to make before powering up the system
for the fi rst time, is to confi rm proper voltage and transformer sizing for
the controller. Each MUA II Controller requires 10 VA of power delivered
to it at 24 VAC. Each 2-slot expansion board requires 5 VA at 24 VAC
and each 4-slot expansion board requires 10 VA at 24 VAC. You may
use separate transformers for each device (preferred) or power several
devices from a common transformer. If several devices are to be powered
from a single transformer, correct polarity must be followed.

Warning: Observe Polarity! All boards must be wired with

GND-to-GND and 24 VAC-to-24 VAC. Failure to

o b s e r v e p o l a r i t y w i l l r e s u l t i n d a m a g e t o

one or more of the boards. Expansion Boards must be

wired in such a way that power to both the expansion

boards and the controller are always powered together.

Loss of power to the expansion board will cause the

controller to become inoperative until power is

restored to the expansion board.