Wiring details, Mua ii controller technical guide 14, Outside air humidity sensor – WattMaster MUA II User Manual

Page 14

Advertising
background image

MUA II Controller

Technical Guide

14

Figure 12: Humidity

Sensor Wiring

GND

INPUTS

GND

AOUT1
AOUT2

GND

+VDC

AIN1
AIN2
AIN3
AIN4
AIN5

AIN7

Outdoor

Air Humidity

Sensor - 4-20mA

Seal All Conduit Fittings
With Silicone Sealant.

MUA II Controller Board

250 Ohm

Resistor

(Shipped With Sensor)

To be Installed Between

AIN5 and GND

The Pull-up Resistor (PU5)
Must Be Removed
When Using A 4-20ma Device

If You Are Using The Standard Factory Supplied Humidity Sensor, It
Has Terminals Labeled “H+ (T1)” And “H- (T4)”. Terminal “H+ (T1)” Is
The Voltage Input And Should Be Connected To The Terminal Labeled
+VDC On The VAV/CAV Controller. Terminal “H- (T4)” Is The 4-20 Ma
Output Signal And Should Be Connected To The Terminal Labeled AIN
5 On The VAV/CAV Controller.

If A Sensor Other Than The One Supplied By The

Factory Is Used, Refer To The Wiring Instructions Shipped With The
Sensor.

A Factory Supplied 250 Ohm Resistor

Should Be Connected Between AIN 5 And A Ground Terminal On The
VAV/CAV Controller.

H-(T4)

H+(T1)

Outside Air Humidity Sensor

If you want to install a humidity sensor onto the MUA II Controller, it
is important that you follow these instructions. There are 2 terminals
labeled “H+” and “H-”. Terminal “H+” will connect to the connection
labeled “+VDC” on the analog input block. See Figure 12. Terminal
“H-” connects to the connection labeled “AIN 5” on the analog input
block. Also, the resistor labeled “PU5” needs to be removed. Lastly, a
supplied 250 Ohm, ¼ Watt, 1% resistor needs to be installed between
“AIN 5” and “GND”. See Figure 12 for detailed wiring.

Warning: It is very important to be certain that all wiring is

correct as shown in the wiring diagram below.

Failure to observe the correct polarity will result in

damage to the Humidity Sensor or controller.

Wiring Details