Large Dehumidifying Dryers

Controls

39

4-4 Dryer Setup

The customer can fine-tune the AP1+ by changing values and turning options on or off.

Use the “Dryer Setup” display to

• Select whether temperatures are displayed in Fahrenheit or Celsius.

• Set the high alarm limit value for the dryer exit air temperature alarm.

• Set the high alarm limit value for the dryer’s after- or pre-cooler option.

• Enable or disable the regeneration closed loop cooling option.

• Set the high alarm limit for the regeneration closed loop cooling option.

Use the “Auto-Tune” display to start or stop auto tuning for the regeneration temperature
control loops.

Use the “Dew Point Setup” display to

• Select whether the regeneration system switches sides when a regeneration cycle

completes (TIME) or when the dew point is greater than a switch point (DEW
POINT).

• Set the high dew point alarm limit value.

• If switch on dew point is selected

o Set the dew point bed switch point value.
o Set the maximum allowed bed in Process (Online) time.

Use the “System Setup” display to

• Set the operator level password and duration.

• Set the setup level password and duration.

• Set the klaxon and alarm lamp suppression time.

Use the “Set Clock” display to set the system time. System time is in 24 hour format.

Use the “Auto-Start” display to set up the 7 day programmable timer.

• Midnight (00:00) is treated as a NO-EVENT

• All other times are in 24 hour format

• Example – Set dryer to start at 6am on Monday and stop at 4pm on Friday:

o Monday on time setting = 06:00
o Friday off time setting = 16:00
o All other values = 00:00
o Auto start option button = ON

Use the “Save and Restore Settings” display to save and restore the AP1+ operational
parameters. Multiple profiles can be used simply by supplying different compact flash
memory cards.