Large Dehumidifying Dryers

Controls

39

4-4 Dryer Setup

The customer can fine-tune the AP1+ by changing values and turning options on or off.

Use the “Dryer Setup” display to

Select whether temperatures are displayed in Fahrenheit or Celsius.

Set the high alarm limit value for the dryer exit air temperature alarm.

Set the high alarm limit value for the dryer’s after- or pre-cooler option.

Enable or disable the regeneration closed loop cooling option.

Set the high alarm limit for the regeneration closed loop cooling option.

Use the “Auto-Tune” display to start or stop auto tuning for the regeneration temperature
control loops.

Use the “Dew Point Setup” display to

• Select whether the regeneration system switches sides when a regeneration cycle

completes (TIME) or when the dew point is greater than a switch point (DEW
POINT).

• Set the high dew point alarm limit value.

• If switch on dew point is selected

o Set the dew point bed switch point value.
o Set the maximum allowed bed in Process (Online) time.

Use the “System Setup” display to

• Set the operator level password and duration.

• Set the setup level password and duration.

• Set the klaxon and alarm lamp suppression time.

Use the “Set Clock” display to set the system time. System time is in 24 hour format.

Use the “Auto-Start” display to set up the 7 day programmable timer.

• Midnight (00:00) is treated as a NO-EVENT

• All other times are in 24 hour format

• Example – Set dryer to start at 6am on Monday and stop at 4pm on Friday:

o Monday on time setting = 06:00
o Friday off time setting = 16:00
o All other values = 00:00
o Auto start option button = ON

Use the “Save and Restore Settings” display to save and restore the AP1+ operational
parameters. Multiple profiles can be used simply by supplying different compact flash
memory cards.