Controls

41

o In addition to temperature setback, close the optional air damper

valve.

Air Balance

o Requires the optional air damper valve.
o Opens the air damper valve when the difference between the return air temperature and

the “Return Air. Temperature Set point” is less than the “Open Deviation” value and
keeps it open until the difference is more than the “Close Deviation” value.