31-DVIE33

9

MINIMUM FIREPLACE DIMENSIONS

J

SIDE

VIEW

TOP VIEW

L

M

K

DIMENSIONS
“Controls Out”

DIMENSIONS

“Controls In”

J

20-1/4” (514 mm)

20-1/4” (514 mm)

K

14” (356 mm)

15 1/2” (394 mm)

L

19” (483 mm)

19” (483 mm)

M

30” (762 mm)

33 1/2” (851 mm)

WARNING:

Failure to position the parts in accordance with these diagrams or failure to use only parts

specifically approved with this appliance may result in property damage or personal injury.

The installer must mechanically attach the marking supplied with the gas fireplace insert to the inside of the firebox of
the fireplace into which the gas fireplace insert is installed.
Cutting of any sheet-metal parts of the fireplace, in which the gas fireplace insert is to be installed, is prohibited.
If the factory-built fireplace has no gas access hole (s) provided, an access hole of 1 1/2” (38.1 mm) or less may be
drilled through the lower sides or bottom of the firebox in a proper workmanship-like manner. This access hole must
be plugged with non-combustible insulation after the gas supply line has been installed.
The fireplace flue damper can be fully blocked open or removed for installation of the gas fireplace insert.
The fireplace and fireplace chimney must be clean and in good working order and constructed of non-combustible
materials. The chimney cleanouts must fit properly.
Refractory, glass doors, screen rails, screen mesh and log grates can be removed from the fireplace before installing
the gas fireplace insert.
Smoke shelves and baffles may be removed if attached by mechanical fasteners. Trim panels must not seal ventila-
tion openings in the fireplace.

Min flue size required 4” (102) x 7” (178)

TOP VIEW

CONTROLS IN

TOP VIEW

CONTROLS OUT