TNC 416/TNC 406/TNC 306

PLC Modules for TNC 416/406

7-113

4.3

Read in Word Range (Module 9010/9011/9012)

A byte, word or double word is read from the defined position in the word memory and returned to
the stack as an output variable. Indexed reading in the memory is possible by specifying a variable
as the name of the memory cell.

Possible errors:
- The defined address is outside the valid range (0..1023).
- Module 9011: The defined address is not a word address (not divisible by 2).
- Module 9012: The defined address is not a double word address (not divisible by 4).

Call:

PS

B/W/D/K

<Number of byte to be read>

(Address)

CM

9010

read byte

PL

B

<byte read>

(Value)

or

PS

B/W/D/K

<Number of word to be read>

(Address)

CM

9011

read word

PL

W

<word read>

(Value)

or

PS

B/W/D/K

<Number of double word to be read>

(Address)

CM

9012

read double word

PL

D

<double word read>

(Value)

Example of Module 9010

STACK

Wortspeicher

35 (80)

35

80

80

B10

B35

B100

..

.
PS B10
CM9010
PL B100

..

.

Error status after call: M3171 =

0: Byte/word/double word was read
1: Error condition see above