9 control word (g1_stw), Control word (g1_stw), Table 18 – HEIDENHAIN PROFIBUS-DP (DPV2) User Manual
Page 47: G1_stw implementation requirements
Advertising

PROFIBUS IO data description
47
5.9 Control word (G1_STW)
The control word controls the functionality of major encoder
functions.
Bit
Function
0...7
Function requests: Reference mark search,
measurement on the fly
8..10
Reserved
11
Home position mode (absolute/relative)
12
Request set/shift of home position (Preset)
13
Request absolute value cyclically
14
Activate parking sensor
15
Acknowledging a sensor error
Table 18
G1_STW implementation requirements
Note: If the sensor parking is activated (bit 14=1) the device
is still on the bus with the slave sign of life active and
encoder error and diagnostics switched off.