10 status word (g1_zsw), Status word (g1_zsw), Table 19 – HEIDENHAIN PROFIBUS-DP (DPV2) User Manual

Page 48: G1_zsw implementation requirements

Advertising
background image

PROFIBUS IO data description

48

5.10 Status word (G1_ZSW)

The status word defines encoder states, acknowledgements,

error messages of major encoder functions.

Bit

Function

0...7

Function status: Reference mark search,

measurement on the fly

8

Probe 1 deflected

9

Probe 2 deflected

10

Reserved, set to zero

11

Requirement of error acknowledgement detected.

12

Set/shift of home position executed

13

Transmit absolute value cyclically

14

Parking sensor active

15

Sensor error

Table 19

G1_ZSW implementation requirements

Note: If bit 13 Transmit absolute value cyclically or bit 15

Sensor error is not set there is no valid value or error
code transferred in G1_XIST2.


Note: Bit 13 Transmit absolute value cyclically cannot be set

at the same time as bit 15 Sensor error as these bits
are used to indicate either a valid position value
transmission (bit 13) or the error code transmission
(bit 15) in G1_XIST2.

Advertising