SMA SB 4200TL HC Multi-String User Manual

Page 17

Advertising
background image

SMA

Technologie AG

Installation Requirements

Installation Guide

SBTLHCMS-IEN080411

Page17

Rating for a Line Circuit Breaker in a Photovoltaic Electrical Power Unit
Operated in Grid-parallel Mode

Various factors should be taken into account when selecting line circuit breakers. These
include, for example:
•

The type of cable used (conductor material and insulation)

•

Ambient temperatures affect the cables (higher temperatures result in a reduced
maximum current load)

•

Method of routing the cable (reduces the ampacity of the conductor)

•

Bundling cables together (reduces the ampacity of the conductor)

•

Loop impedance [Z] (in the event of a body contact this limits the current that can
flow and therefore determines the response behavior of the circuit breaker)

•

Sufficient distance between the circuit breakers so as to avoid undue heating (heat
can trigger the circuit breakers early).

•

Selectivity

•

Protection class of the connected load (VDE 0100, part 410, protection against
electric shock)

For examples for the rating of a line circuit breaker, please refer to section 11 "Rating
for a Line Circuit Breaker" (Page 51)

The Sunny Boy is equipped with an integrated universal current sensitive leakage-cur-
rent monitoring unit. The Sunny Boy can automatically differ between real fault currents
and "normal" capacitive leakage currents.

The following standards should be followed in all cases:

•

DIN VDE 0298-4

(Cable routing and current-carrying capacity)

•

DIN VDE 0100; part 430 (Protective measures "Protection of cable and

cords against overcurrent")

•

DIN VDE 0100; part 410 (Protective measures "Protection against electric

shock")

A 30 mA RCD or FI circuit breaker must not be installed.