8.4. 3 Country-specific Parameter Settings

The parameters listed below represent country-specific settings and are only displayed
in installer mode. All other parameters are international and can be viewed in the table
in section 8.4. 2.

8.4. 4 Non-modifiable Parameters

The following parameters are displayed in the parameter list but cannot be changed:

Name

Short
descr.

Country settings

Germany

Italy

Great Britain

Default

GER/VDE0126-1-1 IT

GB

dFac-Max Hz/s

4.0

0.20

0.25

dZac-Max mOhm 600

350

350

Fac-delta-

Hz

2.45

0.29

0.5

Fac-delta+ Hz

0.19

0.29

0.5

Ni-Test

1

0

0

T-Start

s

2

2

180

Uac-Min

V

198

198

209

Uac-Max

V

260

260

261

Name

Short

descr.

Factory setting

SB 4200TL HC

SB 5000TL HC

Fac-Tavg

ms

160

160

Firmware-DC-BFR

Hardware-DC-
BFR

Plimit

W

4200

5100

SMA-SN

Software-BFR

Software-SRR

Uac-Tavg

ms

80

80