2 grid connection data, Grid connection data – SMA SB 4200TL HC Multi-String User Manual

Page 34

Advertising
background image

Technical Data

SMA

Technologie AG

Page 34

SBTLHCMS-IEN080411

Installation Guide

8. 2 Grid connection data

Description

Short
descrip-
tion

Setting

SB 4200TL HC

SB 5000TL HC

Nominal output power

P

ACnom

4000 W

4600 W

Max. output power

P

ACmax

4200 W

5000 W

Nominal output current

I

ACnom

17.5A

20A

Harmonic distortion of output cur-
rent (at K

Ugrid

< 2 %, P

AC

> 0.5

P

ACnom

)

K

IAC

< 3 %

Operating range, grid voltage

U

AC

180 - 260 V AC
Germany: 198 - 260 V AC

b)

Operating range, grid frequency

f

AC

45.5 - 52.5 Hz
Germany: 47.55 - 50.2 Hz

Phase shift angle (based on the cur-
rent's fundamental frequency)

cos phi

1 (at nominal power output)

Overvoltage category

III

Test voltage (50 Hz)

1.65 kV (1 s routine testing / 5 s type
testing)

Test surge voltage

4 kV (1.2/50 ms)
(serial interface: 6 kV)

Internal consumption in night mode

0.25 W

b)

The Sunny Boy can temporarily feed power into the grid with a maximum output
voltage of 260 V. However, DIN VDE 0126-1-1 stipulates that the 10-minute
average must not exceed a voltage of 253 V. That means, if the grid voltage is
continuously 254 V (e.g.), the inverter disconnects itself from the grid. In this
case, contact the local grid operator for assistance.
DIN VDE 0126-1-1 only applies in Germany. See section 8.4. 3 "Country-spe-
cific Parameter Settings" (Page 43) for
all other preset country values of your
inverter.

Advertising