Installation Requirements

SMA

Technologie AG

Page 20

SBTLHCMS-IEN080411

Installation Guide

The Sunny Boy is designed for operation on 220 - 240 V grids at a grid frequency of
50 Hz. When connecting an inverter to the public grid, follow the connection require-
ments of the local grid operator.

Limit values for AC output

Voltage range
(in the area of application of DIN VDE 0126-1-1)

198 V ... 260 V

a)

Frequency range
(in the area of application of DIN VDE 0126-1-1)

47.55 Hz ... 50.2Hz

Voltage range
(extended operating range)

180V ... 260 V

Frequency range
(extended operating range)

45.5 Hz ... 52.5Hz

a)

The Sunny Boy can temporarily feed power into the grid with a maximum output
voltage of 260 V. However, DIN VDE 0126-1-1 stipulates that the 10-minute
average must not exceed a voltage of 253 V. That means, if the grid voltage is
continuously 254 V (e.g.), the inverter disconnects itself from the grid. In this
case, contact the local grid operator for assistance.
DIN VDE 0126-1-1 only applies in Germany. See section 8.4. 3 "Country-spe-
cific Parameter Settings" (Page 43) for
all other preset country values of your
inverter.