SMA SB 4200TL HC Multi-String User Manual

Page 42

Advertising
background image

Technical Data

SMA

Technologie AG

Page 42

SBTLHCMS-IEN080411

Installation Guide

Ripple-Ctl-Rcvr

enable, disable, auto

auto

Riso-Min

kOhm

1500 ... 30000

1500

Speicherfunkt.

Default Parameter, Reset
Betriebsdaten, Reset Fe-
hler

none

T-Start *

s

2 ... 300

2

Uac-Min *

V

160 ... 230

198

Uac-Max *

V

230 ... 300

260

Usoll-Konst A

V

0 ... 750

290

Usoll-Konst B

V

0 ... 750

290

Parameters designated with * are safety-related grid monitoring parameters. To
change the SMA grid guard parameters, you must enter your personal SMA grid
guard password (Inst.-Code). Please call the SMA Service Line to obtain your per-
sonal SMA grid guard password.

Name

Short
descr.

Value range

Factory setting