Rating for a Line Circuit Breaker

Installation Guide

SBTLHCMS-IEN080411

Page51

11 Rating for a Line Circuit Breaker

Required technical information for the inverters used

Maximum permissible fuse protection for the inverter = 25 A

The choice of cable together with the way it is routed, ambient temperatures and other
underlying conditions limit the maximum fuse protection for the cable.

In our example we assume that the chosen cable (6 mm²) is ideally routed and
can take a nominal current of 32.2 A.

Selecting a line circuit breaker:

The maximum possible nominal current for the cable used and the maximum pos-
sible fuse protection for the inverter now limit the maximum possible nominal cur-
rent for the line circuit breaker.

In our example, 25 A is possible.

However, the thermal suitability of the line circuit breaker still needs to be checked.

Example for the thermal rating for a line circuit breaker in a photovoltaic electrical
power unit operated in grid-parallel mode.
A PV system with 9 inverters type Sunny Boy SB 4200TL HC Multi-String or Sunny
Boy SB 5000TL HC Multi-String is assumed, with 3 inverters per phase.

Maximum output current =

19 A (Sunny Boy SB 4200TL HC Multi-String)

22 A (Sunny Boy SB 5000TL HC Multi-String)