Rating for a Line Circuit Breaker

Installation Guide

SBTLHCMS-IEN080411

Page51

11 Rating for a Line Circuit Breaker

Required technical information for the inverters used

•

Maximum permissible fuse protection for the inverter = 25 A

The choice of cable together with the way it is routed, ambient temperatures and other
underlying conditions limit the maximum fuse protection for the cable.
•

In our example we assume that the chosen cable (6 mm²) is ideally routed and
can take a nominal current of 32.2 A.

Selecting a line circuit breaker:

•

The maximum possible nominal current for the cable used and the maximum pos-
sible fuse protection for the inverter now limit the maximum possible nominal cur-
rent for the line circuit breaker.

•

In our example, 25 A is possible.

However, the thermal suitability of the line circuit breaker still needs to be checked.

Example for the thermal rating for a line circuit breaker in a photovoltaic electrical
power unit operated in grid-parallel mode.
A PV system with 9 inverters type Sunny Boy SB 4200TL HC Multi-String or Sunny
Boy SB 5000TL HC Multi-String is assumed, with 3 inverters per phase.

•

Maximum output current =

19 A (Sunny Boy SB 4200TL HC Multi-String)

22 A (Sunny Boy SB 5000TL HC Multi-String)