6  Maintenance Under Voltage-Free Conditions

Maintenance Manual

SC500-800HE20-WH-en-10

31

6.8 Maintenance after Connecting the Control Voltage

6.8.1 Connecting the Voltage

1. Open the doors of the interface cabinet.
2. Switch on the grid monitoring miniature

circuit-breaker.

3. Connect additional external voltage.
4. Connect external voltage supply externally.
5. Connect AC circuit breaker.
6. Connect the DC voltage in the main distributor or the sub-distributor.
7. Connect the AC voltage of the medium-voltage transformer externally.

8"3/*/(

High voltages that can cause fatal electric shocks are present in the live components of
the inverter.

• Move the key switch to the "Stop" position and ensure it cannot be reconnected accidentally.
• Do not touch any live components in the inverter or the medium-voltage grid. Comply with all

applicable safety regulations for handling medium-voltage grids.

• All previously removed protective covers must be mounted.