3 maintenance intervals – SMA SC 500HE-20 Maintenance Manua User Manual

Page 12

Advertising
background image

3  Maintenance Intervals

SMA Solar Technology AG

12

SC500-800HE20-WH-en-10

Maintenance Manual

3 Maintenance Intervals

Observing maintenance intervals ensures trouble-free operation of the Sunny Central. Maintenance
intervals depend on ambient and operating conditions. Under especially harsh ambient conditions,
certain maintenance tasks must be performed more frequently. These maintenance tasks are listed in
the maintenance report. SMA Solar Technology AG recommends an optical inspection every month
to determine maintenance needs. Under normal ambient and operating conditions, the Sunny Central
must be fully serviced at the following intervals:

Maintenance under normal ambient and operating conditions:

Preventative replacement intervals:

Spare parts

Spare parts can be identified by their reference designation (ref. des.) and the circuit diagram. The
spare parts list includes the item number of each spare part. For information on a specific item number,
please contact the SMA Service Line.

Description

Interval

Routine maintenance

Every 24 months

Description

Interval

Replacing the 24 V power supply units*

* Contact the SMA Service Line.

Every 10 years

Replacing the fans of the inverter bridge*

Every 13 years

Ventilation grid mats

Every 24 months

GFDI/soft grounding relay

100 trippings due to short circuit

Surge arrester

If tripped

Maintenance intervals
Plant size, location and ambient conditions influence the maintenance intervals.

• If the inverter is subject to adverse ambient conditions, SMA Solar Technology AG

recommends shortening the maintenance intervals.