5 Installation Procedure

18

YASKAWA ELECTRIC TOBP C730600 36C 1000-Series Option PG-B3 Installation Manual

Parameter Settings and Connections for Different Encoder Types

Connecting a Single-Pulse Encoder

When using a single-pulse encoder in V/f with PG control mode, connect the pulse output

from the PG to the option and set drive parameter F1-21 to 0.

Connecting a Two-Pulse Encoder

When using a two-pulse encoder, connect the A and B pulse outputs on the PG to the option

and set F1-21 to 1.
When using a two-pulse encoder in Closed Loop Vector control mode, connect pulse outputs

A and B from the encoder to the corresponding terminals on the option.

Connecting a Two-Pulse Encoder with Z Marker Pulse

When using a two-pulse encoder with Z marker pulse, connect the A, B, and Z pulse outputs

to the corresponding terminals on the option.

Control Method

V/f with PG

Closed Loop Vector

No. of Encoders

1 (CN5-C)

2 (CN5-B)

1 (CN5-C)

2 (CN5-B)

Single Pulse (A)

F1-21 = 0

F1-37 = 0

N/A

N/A

Two Pulse (AB Quadrature)

F1-21 = 1

F1-37 = 1

No setting required No setting required

Two Pulse with Marker (ABZ)

F1-21 = 1

F1-37 = 1

No setting required No setting required