6 related parameters – Yaskawa 1000 Series Drive Option - Open Collector Type PG User Manual

Page 27

Advertising
background image

6 Related Parameters

YASKAWA ELECTRIC TOBP C730600 36C 1000-Series Option PG-B3 Installation Manual

27

F1-06

(385)

<3>

PG 1 Ratio for
PG Pulse
Monitor

Sets the division ratio for PG encoder pulse output.
Set as a three-digit number: x is the first digit, y is the
second digit, and z is the third digit:

When only the A pulse is read, this ratio is disabled
and pulses are set as 1/32 : 1.

V/f w/ PG
CLV
CLV/PM

Default: 1
Min: 1
Max: 132

F1-08

(387)

PG Overspeed
Level

Sets the level for detecting overspeed as a percentage
of the maximum output frequency.

V/f w/ PG
CLV
CLV/PM
AOLV/PM

Default: 115
Min: 0
Max: 120

F1-09

(388)

Overspeed Det.
Time

Sets the time required for the motor to exceed the
level set in F1-08 to trigger a fault.

V/f w/ PG
CLV
CLV/PM
AOLV/PM

Default:

<4>

Min: 0.0
Max: 2.0

F1-10

(389)

Excessive
Speed
Deviation Det.
Level

Sets the degree of speed deviation to trigger a dEv
fault. Set as a percentage of the maximum output
frequency.

V/f w/ PG
CLV
CLV/PM
AOLV/PM

Default: 10
Min: 0
Max: 50

F1-11
(38A)

Excessive
Speed
Deviation Det.
Time

Sets the time required a speed deviation situation to
trigger a fault.

V/f w/ PG
CLV
CLV/PM
AOLV/PM

Default: 0.5
Min: 0.0
Max: 10.0

F1-12

(38B)

<3> <5>

PG 1 Gear
Teeth 1

Number of gear teeth between the PG and motor.

A gear ratio of 1 will be used if any of these
parameters is set to 0.

V/f w/ PG

Default: 0
Min: 0
Max: 1000

F1-13

(38C)

<3> <5>

PG 1 Gear
Teeth 2

F1-14
(38D)

PG Disconnect
Det. Time

Sets the time in seconds for PG encoder disconnect to
be detected.

V/f w/ PG
CLV
CLV/PM

Default: 2.0
Min: 0.0
Max: 10.0

F1-18

(3AD)

<3>

Reverse
Rotation Det.
for PG 1

0: Disabled
n: Number of times a dv3 situation must be detected
to trigger a fault.

CLV/PM

Default: 10
Min: 0
Max: 10

F1-19

(3AE)

<3>

Reverse
Rotation Det.
for PG 1

0: Disabled
n: Number of times a dv4 situation must be detected
to trigger a fault.

CLV/PM

Default: 128
Min: 0
Max: 5000

F1-21

(3BC)

<3>

PG 1 Option
Function

0: A pulse detection
1: AB pulse detection

V/f w/ PG

Default: 0
Range: 0, 1

F1-30

(3AA)

<6>

Motor 2 PG
Connector

Selects the PG option connector for motor 2.
0: CN5-C
1: CN5-B

V/f w/ PG
CLV

Default: 1
Range: 0, 1

No.

(Addr. Hex)

Name

Description

Control

Mode

Values

Ratio =

(1 + x)

yz

Pulses

× 60

F1-01

×

F1-13 (load side)

F1-12 (motor side)

Advertising