5 Installation Procedure

YASKAWA ELECTRIC TOBP C730600 36C 1000-Series Option PG-B3 Installation Manual

23

8.

Set drive parameters in

Table 7

for proper motor rotation.

With a two-pulse or three-pulse PG encoder, the leading pulse determines the

motor rotation direction. A PG encoder signal with leading A pulse is considered to

be rotating forward (counter-clockwise when viewing rotation from motor load side).

Figure 12

Figure 12 Displacement of A and B Pulses

After connecting the PG encoder outputs to the option, apply power to the drive and

manually rotate the motor and check the rotation direction by viewing monitor U1-05

on the digital operator.

Reverse motor rotation is indicated by a negative value for U1-05; forward motor

rotation is indicated by a positive value.

If monitor U1-05 indicates that the forward direction is opposite of what is intended,

reverse the two A pulse wires with the two B pulse wires on option terminal TB1 as

shown in

Figure 13

.

Figure 13

Figure 13 A Channel and B Channel Wire Switching

If switching the wires is inconvenient, set drive parameter F1-05/F1-32 to 1 to switch

the direction of how the option reads pulses from the PG encoder output.

Please note that when the drive is initialized using A1-03 =1110, 2220, 3330, the

value for F1-05/F1-32 will reset to factory default and the parameter will need to be

adjusted again to switch the direction.

A pulse

B pulse

The A pulse leads, followed
by the B pulse displaced at 90 degrees

Time

B3

A+ A- B+ B- Z+ Z-

3

4

5

6

A+ A- B+ B- Z+ Z-

5

6

3

4

B3