Electronic Lineshaft with Alignment

Date: 07-01-04, Rev: 04-07

Page 13 of 15

TM.G5SW.046

I Limit

P2-05=2.000 HZ

P2-05 Integral

Limit

Q Q Q Q


This parameter limits the integral part of the position regulator. This parameter should be increased when the
drive will not stay shaft-locked under heavy loads or at high speeds (above base speed). Too high of a setting
will result in instability or overshoot.

D Time

P2-06 = 0.00 sec

P2-06 Derivative

Time

Q Q Q Q


This parameter provides control of the derivative function of the PID speed control loop. Setting this value to zero
will remove any affect that it may have. The derivative provides a means to stabilize the position error if it is
oscillating between plus and minus. Setting this value to high will cause instability.


5.0 New Monitors


Master Encoder

U1-50= 0.00 kHZ

U1-50 Master

Encoder

Q Q Q Q


Displays the pulse frequency of the master encoder.

Slave Reference

U1-51= 0.0 HZ

U1-51 Slave

Reference

Q Q Q Q


Displays the frequency reference of the follower drive prior to ratio adjustments. The follower will not exceed its
maximum output frequency based on E1-04 and D2-01.

Setting Range:

0.000 to 20.000

Factory Default:

2000

MODBUS Address:

0594H

Setting Range:

0.00 to 100.00

Factory Default:

0.00

MODBUS Address:

0595H

Range:

0.00 to 327.67 kHz

MODBUS Address:

00D0H

Range:

-999.9 to 3276.7 Hz

MODBUS Address:

00D1H