Yaskawa J7 to J1000 User Manual

Page 13

Advertising
background image

(Header Title) Application Note


Doc#: PL.J1000.01 Copyright Yaskawa Electric America, Inc.©2008 www.yaskawa.com August 1, 2008 13 of 19

Subject: Transition Guide

Product: J1000

Document: PL.J1000.01

Title: Product Transition Guide – J7 to J1000

Product Transition Guide – J7 to J1000

J7

J1000

Drive

Function
/ Parameter

Parameter

No.

Initial

Value

Parameter

No.

Initial

Value

Comments

Frequency Reference
from Operator ENTER
Key Selection

n08 0

o2-05 0

J7 J1000

n08 Æ 0

o2-05 Æ 0

n08 Æ 1

o2-05 Æ 1

Maximum Output
Frequency

n09

60.0 Hz

E1-04

60.0 Hz

Maximum Output
Voltage

n10

200.0V*

E1-05

200 V*

* Values for a 400 V class drive are double.

Base Frequency

n11

60.0 Hz

E1-06

60.0 Hz

Middle Output
Frequency

n12

1.5 Hz

E1-07

3.0 Hz

Middle Output Voltage

n13

12.0 V*

E1-08

16.0 V*

* Values for a 400 V class drive are double.

Minimum Output
Frequency

n14

1.5 Hz

E1-09

1.5 Hz

Minimum Output
Voltage

n15

12.0 V*

E1-10

12.0 V*

* Values for a 400 V class drive are double.

Acceleration Time 1

n16

10.0 s

C1-01

10.0 s

Deceleration Time 1

n17

10.0 s

C1-02

10.0 s

Acceleration Time 2

n18

10.0 s

C1-03

10.0 s

Deceleration Time 2

n19

10.0 s

C1-04

10.0 s

S –Curve at
Acceleration Start

C2-01

S-Curve at Acceleration
End

C2-02

S-Curve at Deceleration
Start

C2-03

0.2 s

S-Curve at Deceleration
End

n20

0 (0 s)

C2-04 0.0

s

J7:

Selection parameter (setting 0, 1, 2 and 3).

Same setting for all conditions.

J1000:

Numerical parameter (time must be set in

seconds). The S-Curve is set separately for

each accel / decel profile selection.

Multiple Speed Ref. 1

n21

6.00 Hz

d1-01

0.00 Hz

Multiple Speed Ref. 2

n22

0.00 Hz

d1-02

0.00 Hz

Multiple Speed Ref. 3

n23

0.00 Hz

d1-03

0.00 Hz

Multiple Speed Ref. 4

n24

0.00 Hz

d1-04

0.00 Hz

Multiple Speed Ref. 5

n25

0.00 Hz

d1-05

0.00 Hz

Multiple Speed Ref. 6

n26

0.00 Hz

d1-06

0.00 Hz

Multiple Speed Ref. 7

n27

0.00 Hz

d1-07

0.00 Hz

Multiple Speed Ref. 8

n28

0.00 Hz

d1-08

0.00 Hz

Jog Frequency

n29

6.00 Hz

d1-17

6.00 Hz

Frequency Reference
Upper Limit

n30 100%

d2-01 100%

Frequency Reference
Lower Limit

n31 0%

d2-02

0.0%

Motor Rated Current

n32 —

E2-01 —

Depends on the drive capacity.

Motor Overheat
Protection

n33 0

L1-01 1

J7 J1000

n33 Æ 0

L1-01 Æ 1

n33 Æ 1

L1-01 Æ 2

n33 Æ 2

L1-01 Æ 0