Product Transition Guide – J7 to J1000
4.5 Control Terminal and Wire Sizes
Voltage
Class
Drive
Terminal Symbol
Screw
Size
Tightening
Torque
N.m
(lb - in.)
Wire Size
mm
2
(AWG)
Recommended
Wire Size
mm
2
(AWG)
J7
S1 - S5, SC, FS, FR,
FC, AM, AC
Flexible: 0.5 ~ 0.75
(20 to 18)
Solid: 0.5 ~ 1.25
(20 to 18)
J1000
S1 - S5, SC, V+, A1,
AC, AM, AC
M2
0.22 ~ 0.25
(1.9 to 2.2)
Flexible: 0.25 ~ 1.0
(24 to 18)
Solid: 0.25 ~ 1.5
(24 to 16)
0.75
(18)
J7
Flexible: 0.5 ~ 0.75
(20 to 18)
Solid: 0.5 ~ 1.25
(20 to 18)
All
J1000
MA, MB, MC
M3
0.5 ~ 0.6
(4.4 to 5.3)
Flexible: 0.25 ~ 1.0
(24 to 18)
Solid: 0.25 ~ 1.5
(24 to 16)
0.75