Yaskawa J7 to J1000 User Manual

Page 17

Advertising
background image

(Header Title) Application Note


Doc#: PL.J1000.01 Copyright Yaskawa Electric America, Inc.©2008 www.yaskawa.com August 1, 2008 17 of 19

Subject: Transition Guide

Product: J1000

Document: PL.J1000.01

Title: Product Transition Guide – J7 to J1000

Product Transition Guide – J7 to J1000

J7

J1000

Drive

Function
/ Parameter

Parameter

No.

Initial

Value

Parameter

No.

Initial

Value

Comments

Over Torque Detection
Level

n60 160%

L6-02 150%

Over Torque Detection
Time

n61

0.1 s

L6-03

0.1 s

Frequency Reference
Hole Selection
(Up / Down Function)

n62 0

d4-01 0

J7 J1000

n62 Æ 0

d4-01 Æ 0

n62 Æ 1

d4-01 Æ 1

Torque Compensation
Gain

n63 1.0

C4-01

1.00

Motor Rated Slip

n64

E2-02

Default value depends on the drive capacity.

Motor No-Load Current

n65 —

E2-03 —

Default value depends on the drive capacity.

Set E2-03 = n32* n65 / 100%

Slip Compensation Gain

n66 0.0

C3-01 0.0

Slip Compensation
Time Constant

n67

2.0 s

C3-02

2000 ms

J7: Setting unit is 1.0 s

J1000: Setting unit is 1 ms

MEMOBUS / Modbus
Communication Error
Behavior Selection

n68 0

H5-04

H5-05

3 —

MEMOBUS / Modbus
Communication Error
Detection

— —

H5-05 1

J1000

J7

H5-04 H5-05

n68 Æ 0

1

n68 Æ 1

0 (C1-02)

n68 Æ 2

2 (C1-09)

n68 Æ 3

3

1

n68 Æ 4

No effect

0

MEMOBUS / Modbus
Frequency Reference
and Monitor Units

n69 0

H5-13 0

J7 J1000

n69 Æ 0

H5-13 Æ 0

n69 Æ 1

H5-13 Æ 1 and

o1-03 Æ 0

n69 Æ 2

H5-13 Æ 2

n69 Æ 3

H5-13 Æ 3

MEMOBUS / Modbus
Slave Address

n70 0

H5-01

1F

J7: Set as decimal value.

J1000: Set as hexadecimal value.

MEMOBUS / Modbus
Communication Speed
Selection

n71 2

H5-02 3

J7 J1000

n71 Æ 0

H5-02 Æ 1

n71 Æ 1

H5-02 Æ 2

n71 Æ 2

H5-02 Æ 3

n71 Æ 3

H5-02 Æ 4

MEMOBUS / Modbus
Parity Selection

n72 0

H5-03 0

J7 J1000

n72 Æ 0

H5-03 Æ 1

n72 Æ 1

H5-03 Æ 2

n72 Æ 2

H5-03 Æ 0

Transmission Wait Time

n73

10 ms

H5-06

10 ms

Advertising