(Header Title) Application Note


Doc#: PL.J1000.01 Copyright Yaskawa Electric America, Inc.©2008 www.yaskawa.com August 1, 2008 14 of 19

Subject: Transition Guide

Product: J1000

Document: PL.J1000.01

Title: Product Transition Guide – J7 to J1000

Product Transition Guide – J7 to J1000

J7

J1000

Drive

Function
/ Parameter

Parameter

No.

Initial

Value

Parameter

No.

Initial

Value

Comments

Motor Protection Time
Constant

n34

8 min

L1-02

1 min

Set L1-02 = n34 / 8.

Drive Cooling Fan
Operation Selection

n35 0

L8-10 0

J7 J1000

n35 Æ 0

L8-10 Æ 0

n35 Æ 1

L8-10 Æ 1

Terminal S1 Function
Selection

— —

H1-01

40

The function of S1 is fixed to Fwd Run in the

J7. The equivalent setting in the J1000 is

H1-01 = 40 (default).

Terminal S2 Function
Selection

n36 2

H1-02

41

Terminal S3 Function
Selection

n37 5

H1-03

24

Terminal S4 Function
Selection

n38 3

H1-04

14

J7 J1000

n36 ~ 39 Æ 2

H1-02 ~ 05 Æ 41

n36 ~ 39 Æ 3

H1-02 ~ 05 Æ 24

n36 ~ 39 Æ 4

H1-02 ~ 05 Æ 25

n36 ~ 39 Æ 5

H1-02 ~ 05 Æ 14

n36 ~ 39 Æ 6

H1-02 ~ 05 Æ 3

n36 ~ 39 Æ 7

H1-02 ~ 05 Æ 4

n36 ~ 39 Æ 8

H1-02 ~ 05 Æ 5

n36 ~ 39 Æ 10

H1-02 ~ 05 Æ 6

n36 ~ 39 Æ 11

H1-02 ~ 05 Æ 7

n36 ~ 39 Æ 12

H1-02 ~ 05 Æ 8

n36 ~ 39 Æ 13

H1-02 ~ 05 Æ 9

n36 ~ 39 Æ 14

H1-02 ~ 05 Æ 61

n36 ~ 39 Æ 15

H1-02 ~ 05 Æ 62

n36 ~ 39 Æ 16

H1-02 ~ 05 Æ A

n36 ~ 39 Æ 17

H1-02 ~ 05 Æ 1

n36 ~ 39 Æ 18

H1-02 ~ 05 Æ 2

n36 ~ 39 Æ 19

n04 Æ 0

H1-02 ~ 05 Æ 28

Set the stop time C1-

09

n36 ~ 39 Æ 19

n04 Æ 1

H1-02 ~ 05 Æ 24

n36 ~ 39 Æ 20

n04 Æ 0

H1-02 ~ 05 Æ 15

Set stop time C1-09,

no alarm message

.

n36 ~ 39 Æ 20

n04 Æ 1

Can not be set.

n36 ~ 39 Æ 21

n04 Æ 0

H1-02 ~ 05 Æ 29

Set the stop time

C1-09

n36 ~ 39 Æ 21

n04 Æ 1

H1-02 ~ 05 Æ 25

n36 ~ 39 Æ 22

n04 Æ 0

H1-02 ~ 05 Æ 17

Set stop time C1-09,

no alarm message

.

n36 ~ 39 Æ 22

n04 Æ 1

Can not be set.