Yaskawa 545 PLC User Manual
Page 14
 
4
OPERATION
13
PLC Gateway Display Messages
4/12/94
PUPn
n=3 – During this stage, the PLC Gateway checks
(cont’d)
each base on its list and makes sure the base 
has received configuration information from the 
Texas Instruments PLC. If not, an "ECdd" 
message is displayed, where "dd" is the base 
number of the base that has not responded. 
If all drops on the list are configured, then the 
gateway issues another power-up message 
across the network and enters the RUN stage.
RUN
When this message is displayed, the PLC Gateway 
has completed its power-up (PUP) sequence and is 
ready to transfer data to and from the Texas 
Instruments PLC. If, while in this stage, an alloca-
tion message is received for a drop that has not been 
configured, the PLC Gateway jumps back to the PUP 
sequence. A "ECOM" error also causes the PLC 
Interface to leave the RUN stage and return to the 
PUP stage when communication is re-established 
between the 5136-TI card and the Texas 
Instruments RBS Processor.
THNP
This message is displayed during PLC Interface
Check that the 5136-TI card
has
initialization if it is determined that the 5136-TI
been properly installed. The 5136-TI
card is not present.
card could be defective; swap it with 
another that you know works 
properly.
TIFL
This message is displayed during PLC Gateway
or
initialization if the 5136-TI card software never com-
TNR
pletes its own initialization and remains not ready.
TQFL
Transmission Queue Full. This generally occurs
• Reduce number of data points.
when the amount of data requested exceeds the
• Change update rates in the PAC
gateway bandwidth.
program.
• If multiple drives are requesting
the same data, change the PAC 
programs so that one drive 
requests the data and then passes 
it to the other drives.
• Add additional gateways to share
the load.
Table 7. PLC Gateway Display Messages (Continued)
MESSAGE
DESCRIPTION
TROUBLESHOOTING
RD 3056-10