3

OPERATION

6

Programming the PAC Blocks

4/12/94

3. The PLC gateway can only access modules in slots 1 to 16.
If you define modules in other bases and slots, you can not
access them through the PLC gateway.

4. Modules can only be of types 16Y (Discrete Output), 16X
(Discrete Input), 8WY (8 Channel Register Output), or 8WX
(8 Channel Register Input).

The PLC gateway receives messages from the MicroTrac LAN. Each of these
messages contains a channel number. This channel number specifies which
Modicon module the message is addressing. The channel number can range
from 011 to 249. The least significant digit is used to specify the slot number,
and the 2 most significant digits specify the drop number. The rack is always
assumed to be 2. When dealing with analog data, there is always a sub
channel field that specifies the word within th analog module the message is
addressing. This can range from 1 to 8. The discrete messages have a mask
field which specifies the bits the message is addressing.

Table 5. Module Types

PAC

TEXAS INSTRUMENTS PLC MODULE

BLOCK

TYPE

DESCRIPTION

LOGO

16X

16 point Discrete Input Module

NUMO

8WX

8 channel Register Input Module

LOGI

16Y

16 point Discrete Output Module

NUMI

8WY

8 channel Register Output Module

Programming

the PAC Blocks

Table 6. Channel Number Designations

LAN Node

LAN Channel

LAN Sub Channel

Number

Number

NUMBER

200 -

XX

X

- XX

TI

TI

TI

Slot No.

Base No.

Bit No.

Range =

Range =

Range = 01 to 16 for

01 to 16

01 to 09

Logic I/O

Range = 01 to 08 for

Numeric I/O

RD 3056-10