Texas Instruments PLC Troubleshooting

4/12/94

Texas

Instruments

PLC

Troubleshooting

This section contains a list of scenarios and possible causes pertaining to
communications problems that may be encountered with the 5136-TI Direct
Link Interface card and the TI 545 PLC.

As a first check, the red and green LEDs on the face of the card provide a
quick visual indication as to the state of the card. Table 8 indicates what is to
be expected after a successful installation of the 5136-TI firmware module.

If communications are not taking place between the 5136-TI card and the PLC,
check per Table 9.

Table 8. 5136-TI LED Indications

RED GREEN

CONDITION

ON

ON

Card is in a reset state. The
TI RDC software module has
not yet been loaded onto the
card.

OFF

DIM

Card is executing software
and communications are
taking place. No configur-
ation information exists.

OFF

BRIGHT

Card is executing software
and communications are
taking place. Data for a
created RBC is being
updated.

OFF

OFF

Card is executing software,
but no communications to
the card are taking place.

Table 9. Checking for No Communications

TROUBLE

INDICATOR

POSSIBLE CAUSE

Green LED OFF

1. Cabling to card is

all the time.

incorrect or disconnected.

2. Cabling to PLC is

incorrect or disconnected.

3. PLC is powered off.

4. No bases or modules

have been allocated by
any drives.

RD 3056-10