Yaskawa Modicon 800 Series Remote I/O Network for use on Microtrac LAN User Manual

Page 21

Advertising
background image

4

OPERATION

20

PLC Gateway Status

5/24/96

display

meaning

PUPn

Displayed after the

n = 1 During this stage the PLC

gateway has

gateway broadcasts a power-up

successfully

message across the MicroTrac

completed

LAN. Also, if the PLC

initialization and is

gateway has returned to the

ready to receive

PUP sequence because of an

messages from the

"ECOM" error (see ECOM

network.

message description) and
communication has been
re-established, then internal
tables are also cleared.

n = 2 During this stage, the PLC

gateway is decoding allocation
messages (types 10, 11, 12, 13
and 2D) and setting up
simulated drops on the
interface card. A list of all
the drops requested via the
allocation messages is also
made. If after four seconds
no allocation messages are
received, then the PLC
gateway proceeds to the next
step.

n = 3 During this stage the PLC

gateway checks each drop on
its list and makes sure the drop
has received configuration
information form the Modicon
PLC. If not, an "ECdd"
message is displayed, where
"dd" is the drop number of the
drop that has not responded.
If all drops on the list are
configured, then the gateway
issues another power-up
message across the network
and enters the RUN stage.

PLC Gateway

Status

(continued)

RD 3004-20