PLC Gateway Status

5/24/96

display

meaning

ENIA

When the PLC gateway receives a numeric input allocation
message, this error message could appear for one of the
following reasons:

• The internal allocation table is full and cannot handle

another allocation. The allocation table has room for
1024 allocations. A numeric allocation uses 8
elements in the table.

• The subchannel is out of range. It can range from 1

to 8.

ENOA

When the PLC gateway receives a numeric output allocation
message from the network, this error message could appear
for any of the following reasons:

• The internal allocation table is full and cannot handle

another allocation. The allocation table has room for
1024 allocation. A numeric allocation uses 8
elements in the table.

• The subchannel is out of range. It can range from 1

to 8.

• The subchannel has already been allocated by another

node.

ERDU

When the PLC gateway receives a PLC configuration
message, this error message appears if the internal RDU table
is full and cannot accommodate another entry. The table has
a capacity of 255 entries. The PLC Configuration message is
ignored.