VS-616G5 Option Instruction Manual: Profibus-DP Control Card SI-P

Table 8: Fast I/O Input Data Details (G5 SI-P

PDP Master)

Byte #

Function

Contents

Description

0

Operation Command

High byte of the Operation Command

See Table 9

1

Low byte of the Operation Command

2

Speed Command

High byte of the 16bit Hexadecimal data

1 / 0.01Hz

3

Low byte of the 16bit Hexadecimal data

4

Torque Reference /

Limit

High byte of the 16bit Hexadecimal data

FVC mode only

1 / 0/1%

5

Low byte of the 16bit Hexadecimal data

6

Torque Compensation

High byte of the 16bit Hexadecimal data

with PG only

1 / 0.01Hz

7

Low byte of the 16bit Hexadecimal data

8

Not Used

9

Not Used

10

AO CH1 (Terminal 21)

Output

High byte of the 16bit Hexadecimal data

-726 (-11V) to 726 (11V)

Effective when H4-01=”1F”

11

Low byte of the 16bit Hexadecimal data

12

AO CH1 (Terminal 23)

Output

High byte of the 16bit Hexadecimal data

-726 (-11V) to 726 (11V)

Effective when H4-04=”1F”

13

Low byte of the 16bit Hexadecimal data

14

DO Output

Bit 0 = Terminal 9-10 Effective when H2-01=”F”
Bit 1 = Terminal 25-27 Effective when H2-02=”F”
Bit 2 = Terminal 26-37 Effective when H2-03=”F”
Bit 3 to F must be “0”

15

Must be “0”

Table 9: Bytes 0 and 1 of Fast I/O Input Data

Byte #

Bit #

Description

Remarks

0

0

Forward Run

Effective when the setting B1-02=3

1

Reverse Run

Effective when the setting B1-02=3

2

Terminal 3 Function

Depends on H1-01 setting

3

Terminal 4 Function

Depends on H1-02 setting

4

Terminal 5 Function

Depends on H1-03 setting

5

Terminal 6 Function

Depends on H1-04 setting

6

Terminal 7 Function

Depends on H1-05 setting

7

Terminal 8 Function

Depends on H1-06 setting

1

0

External Fault

1

Fault Reset

2

Not Used

3

Not Used

4

Not Used

5

Not Used

6

Not Used

7

Not Used